Installation guide

SFP extraction tool kit
China RoHS guide
Cable management comb
Brocade-branded USB device
Power cord retainer kit
Hardware for securing the device in a rack
Web pointer document
Air filter
Line cards (up to eight) and additional power supplies must be ordered separately.
The rack mount kits must be ordered separately.
Brocade-branded transceivers (SFP, SFP+, CFP2, QSFP, or 10Base-T) and cables or direct-attach
cables must also be ordered separately. The Brocade VDX 8770-8 supports SR and LR SFP, SFP+,
and CFP2 transceivers. QSFP transceivers are SR transceivers only. Twinax active copper and fiber-
optic breakout cables are supported.
For details on supported transceivers, refer to the following publications:
Brocade VDX Transceiver Support Matrix at http://www.brocade.com/downloads/documents/
matrices/brocade-vdx-sfp-transceivers-mx.pdf.
Brocade Ethernet Optics Family data sheet at http://www.brocade.com/downloads/documents/
data_sheets/product_data_sheets/brocade-ethernet-optics-family-ds.pdf.
NEBS requirements
The following table lists the installation requirements for meeting NEBS GR-1089 compliancy.
NEBS installation requirements TABLE 4
Reference Warning, requirement, or statement
Intrabuilding or Intra-
connection
WARNING: The intra-building copper Ethernet ports of the equipment or subassembly
are suitable for connection to intrabuilding or unexposed wiring or cabling only. The
intra-building ports of the equipment or subassembly MUST NOT be metallically
connected to interfaces that connect to the outside plant (OSP) or its wiring. These
interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4 ports
as described in GR-1089-CORE, Issue 6) and require isolation from the exposed OSP
cabling. The addition of Primary Protectors is not sufficient protection in order to
connect these interfaces metallically to OSP wiring.
First Level Lightning
Criteria AC Power Ports
WARNING: The Brocade device must be connected to external Special Protection
Devices (SPD) when installed and connected to commercial AC power.
Class A2 Voltage
Accessibility
The Brocade device must be located in a restricted access location were only crafts
personnel are allowed access.
Class B Voltage
Accessibility
The Brocade device must be located in a restricted access location were only crafts
personnel are allowed access.
Equipment Grounding
Systems
The Brocade device must be installed and connected to the CBN, IBN, or Ether.
Communication
Equipment Grounding
The Brocade device is suitable for connection to the Central Office.
NEBS requirements
Brocade VDX 8770-8 Hardware Installation Guide 21