Chapter
5
Removal and Replacement Procedures
In this chapter
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
ESD precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Cable management finger assembly removal and replacement . . . . . . . . . 58
Line card removal and replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Management module removal and replacement . . . . . . . . . . . . . . . . . . . . . 62
Switch fabric module removal and replacement. . . . . . . . . . . . . . . . . . . . . . 65
Power supply removal and replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Fan removal and replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Air filter removal and replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Module filler panel removal and replacement . . . . . . . . . . . . . . . . . . . . . . . 74
Chassis ID card removal and replacement . . . . . . . . . . . . . . . . . . . . . . . . . . 75
SFP transceiver removal and replacement . . . . . . . . . . . . . . . . . . . . . . . . . . 76
QSFP transceiver removal and replacement . . . . . . . . . . . . . . . . . . . . . . . . . 78
Cable routing table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Introduction
NOTE
Refer to Appendix B, “Caution and Danger Notices” before servicing.
The field-replaceable units (FRUs) in the Brocade VDX 8770-4 can be removed and replaced
without special tools. The Brocade VDX 8770-4 can continue operating during many of the FRU
replacements if the conditions specified in the procedures are followed.
The following sections contain FRU removal and replacement procedures.
ESD precautions
The Brocade VDX 8770-4 contains ESD-sensitive FRUs. When working with any Brocade VDX
8770-4 FRU, use correct electrostatic discharge (ESD) procedures.
Wear a wrist grounding strap connected to chassis ground (if the Brocade VDX 8770-4 is
plugged in) or a bench ground. Refer to “Port side of the Brocade VDX 8770-4” on page 3 for
the location of the ESD jack.
Store ESD-sensitive components in anti-static packaging.