System information
Dell
PowerEdge M1000e Technical Guide 31
The following information is also applicable for half-height blade servers:
Throttling (performance reduction to conserve power):
o 220–240V power:
2 PSUs—Throttling will occur if heavily configured blades are worked very hard
at the same time.
3 PSUs:
130W processors—Some throttling will occur if heavily configured blades
are worked hard at the same time.
95W or 80W processors—Throttling may happen if all servers are run
under a very heavy load.
4 or 5 PSUs—No throttling will occur.
o 110V power—Throttling will occur in all power-supply configurations if a full set of
heavily configured blades are worked hard at the same time.
Prioritized performance—Under throttling conditions, there will be a performance impact on
the lower-priority servers.
o Dell recommends you choose which servers are prioritized through CMC’s prioritization
feature.
o Multiple low-priority servers can spread out the impact of prioritization. If all servers
are the same priority, they would each experience a slight performance impact as the
throttling would be passed from server to server.
Delayed power-ups—When pushing the limits of the guidelines listed in Table 11, 1–3 servers
may not be powered on during the initial power-up sequence if all servers were started
simultaneously. The servers may need to be powered on in a second power-up action after
the initial blades go through their post-boot power inventory and allocation.
Dell recommends that all customers running a power-hungry configuration should install the modular
iDRAC firmware 3.02 upgrade, which contains the following enhancements:
Improved calculation for power budgeting to enable more servers to be powered up
simultaneously.
Functionality to enable iDRAC to retry power up for blade servers automatically in the event
that some servers do not power up initially due to the pre-boot power inventory.
5.2.6.2 Full-height Blade Servers
0 lists the maximum number of recommended half-height blade servers per power-supply
configuration according to the following server definitions:
Light configuration: 2 x 95W processor, 4 DIMMs
Medium configuration: 4 x 105W or 2 x 130W processors, 16 DIMMs
Heavy configuration: 4 x 105W or 2 x 130W processors, 32 DIMMs