Installation guide

14 Brocade ICX 6430-C Compact Switch Hardware Installation Guide
53-1002817-02
Preparing the installation site
2
Preparing the installation site
Before installing the device, plan its location and orientation relative to other devices and
equipment.
Cabling infrastructure
Ensure that the proper cabling is installed at the site. For information about supported SFP and
SFP+ transceivers and cable lengths and types, refer to the following Brocade website:
http://www.brocade.com/downloads/documents/data_sheets/product_data_sheets/Optics_
DS.pdf
Installation location
Devices can be mounted in a standard 19-inch equipment rack, on a flat surface, on a wall, or on a
metal surface.
The site should meet the following requirements:
Maintain the operating environment as specified in the section “Environmental
considerations” on page 38.
Allow a minimum of 7.62 cm (3 in.) of space above the device and between the front and the
back of the device and walls or other obstructions for proper airflow.
Allow at least 7.62 cm (3 in.) of space at the front and back of the device for the twisted-pair,
fiber-optic, and power cabling.
The site should be accessible for installing, cabling and maintaining the devices.
Allow the status LEDs to be clearly visible.
Allow for twisted-pair cables to be routed away from power lines, fluorescent lighting fixtures,
and other sources of electrical interference, such as radios and transmitters.
Allow for the unit to be connected to a separate grounded power outlet that provides 100 to
240 VAC, 50 to 60 Hz, is within 2 m (6.6 ft) of each device, and is powered from an
independent circuit breaker. As with any equipment, a filter or surge suppressor is
recommended.
For a 2-post rail mount configuration, order the appropriate mounting kit and refer to the kit
documentation.
When using the magnet mount installation to install the device on a metal surface, the device
cannot be installed above 1.9 meters.
Rack-mount installation considerations
Before mounting the device in a rack, ensure that the following rack-mount installation
requirements are met:
Allow a minimum of 7.62 cm (3 in.) of space above the device and between the front and the
back of the device and walls or other obstructions for proper airflow.
Temperature: Because the temperature within a rack assembly may be higher than the
ambient room temperature, check that the rack-environment temperature is within the
specified operating temperature range. (Refer to “Operating environment” on page 38.)