Installation guide
Brocade ServerIron ADX Installation Guide 19
53-1003445-01
Installing ServerIron ADX
2
CAUTION
For a DC system, use a grounding wire of at least 6 American Wire Gauge (AWG). The 6 AWG wire
should be attached to an agency-approved crimp connector, crimped with the proper tool.
This Caution Applies to the ServerIron ADX 1000
CAUTION
For the DC input circuit to the system, it must be connected to a 20 amp circuit breaker, minimum
-48Vdc, double pole, on the input to the terminal block. The input wiring for connection to the
product should be copper wire, 12 AWG, marked VW-1, and rated minimum 90 degrees Celsius.
This Caution Applies to the ServerIron ADX 4000, ServerIron ADX 8000 and
ServerIron ADX 10000
CAUTION
For an AC system, use a ground wire of at least 6 American Wire Gauge (AWG). The ground wire
should have an agency-approved crimped connector (provided with the chassis) attached to one
end, with the other end attached to building ground. The connector must be crimped with the
proper tool, allowing it to be connected to both ground screws on the enclosure.
CAUTION
For the DC input circuit to the system, it must be connected to a 40 amp circuit breaker, minimum
-48Vdc, double pole, on the input to the terminal block. The input wiring for connection to the
product should be copper wire, 8 AWG, marked VW-1, and rated minimum 90 degrees Celsius.
Installing ServerIron ADX
This section describes the steps to install a ServerIron ADX:
• “Preparing the installation site”
• “Installing the ServerIron ADX chassis in a rack”
• “Installing modules in ServerIron ADX chassis devices”
• “Installing power supplies”
• “Connecting AC power”
• “Connecting DC power to a chassis”
• “Attaching a PC or terminal to the Console port or Ethernet port”
• “Attaching a management station”