Specification Sheet

A&E Specs
Performance Requirements
Damper shall be motorized.
Damper shall be sealed.
Intelligence Requirements
Unit shall measure temperature and dew point every hour and keep the data of the last 48 hours in memory.
Unit shall be capable of measuring the operating time of heating and cooling operation from the thermostat and keep the
data of the last 48 hours in memory.
Unit shall be able to stop ventilation when temperature or dew point is outside the preset limits.
Unit’s preset limits shall be dierent when heating/cooling is operating than when heating/cooling is not operating.
Construction Requirements
Unit’s housing shall be made of 24 ga galvannealed steel.
Unit’s width shall not exceed 10 5/8 in.
Unit’s height shall not exceed 7 3/4 in.
Unit’s housing’s length shall not exceed 6 3/8 in. including ports
Unit’s weight shall not exceed 2.5 pounds
Unit shall be UL, CSA or ETL certied and conform to UL1995
Quality Requirements
Unit shall be protected by a 5-year limited warranty.
Unit shall be ASHRAE 62.2-2010/2016/2019 and IRC/IMC compliant.
Manufacturer shall be ISO 9001-2015.
Installation requirements
Unit shall be suitable to be mounted and sealed directly on the AHU.
Unit shall be suitable for horizontal through surface, suspended, side, below, or above surface mount.
Unit shall be designed to allow for horizontal or vertical airow path.
Unit’s ports shall be 6-in. round.
Unit’s port shall include a vapor barrier ring.
Unit shall include a removable terminal block for wiring connections.
Sensor shall be integrated to unit to ensure proper reading.
Control shall be integrated to unit.
Unit shall include a protection to avoid accidental changes of settings after installation.
1103516B