Specification Sheet

Filters
2 washable  lters, 20 PPI.
MERV 7 optional  lters, part 21030.
Product balancing
The ERVS100 is equipped with 2 high static pressure blowers and is balanced at the factory. At installation, the ERVS100 will remain balanced
(within 10% di erence between the exhaust and supply air ows) when the static pressure di erence between the exhaust and the supply remains
below 0.2 in. wg. after all ducting is installed. No balancing is required when this condition is met.
Performance in winter season
VF0066
Supply air from
outside
32°F @ 30% RH
Exhaust to
outside
45°F @ 36% RH
Exhaust from
home
75°F @ 50% RH
Supply to
home
63°F @ 40% RH
Defrosting system
Unit operates a negative defrost during 10 minutes every 20 minutes when outside temperature is below 14°F and 10 minutes every
10 minutes below -4°F
Energy Recovery Core
Material: Polymerized paper
Type: Cross  ow
Warranty 5 years
Options
Broan VB20W 20 min push-button control
Broan 69V Single-Function Control, Ivory (Dry contact standby switch)
Broan 69W Single-Function Control, White (Dry contact standby switch)
Broan 634M black exhaust roof cap 6" with backdraft damper and bird screen
Broan 843BL black exhaust wall cap 6" with backdraft damper and bird screen
Broan 641 aluminum exhaust wall cap 6"
Broan EH6 aluminium inlet wall cap 6" with bird screen
Broan 641FA aluminum inlet wall cap 6" with bird screen
Broan CVG6 interior inlet plastic grille 6"
Broan CVL6 mounting sleeve for inlet grille CVG6
Broan CVLD6 sleeve with 6" backdraft damper