Specification Sheet
Project: REMARKS
Location:
Part no.: ERV100SP
Qty.:
Submitted by: Date:
Broan ErV100 PLUS arcHitEctUraL SPEcificationS
AIRFLOW
• High static pressure backward blowers shall perform a minimum of
68 CFM @ 1.0 in. w.g.
• Optional high speed: 85 CFM
• Optional low speed: 65 CFM
CONSTRUCTION
• Housing shall be made of 22 ga. galvanized steel
• Door shall be made of 22 ga. pre-painted steel
• Insulation shall be made of one-piece molded expanded polystyrene,
UL 94 HF-1 certied
• 5" diameter ports shall be made of galvanized steel
• Door hinges and latches shall be made of steel
• Cold side ports shall have plastic ring to allow vapor barrier sealing
• Unit construction and components shall be UL and CSA certied
• Unit shall operate all year long without drain
• Weight shall not exceed 35 lb.
• Fresh air from outside and Exhaust air to outside ports shall be located
on same side
• Backdraft damper shall be integrated in cold exhaust ports
• ERV unit shall be HVI certied and ENERGY STAR® qualied
MOTORS
• Unit shall have two high reliability, external rotor PSC motors, totally
enclosed and thermally protected
• The backward blowers shall support high static pressure environment
• The insulation class shall be B
FILTERS
• ERV unit shall have two washable 20 ppi reticulated polyester
urethane foam lters, UL 900 class 2 certied
• Optional MERV 7 lter kit shall be available
ERV CORE
• The ERV core shall be a crossow aluminum-polymerized paper core,
UL723 certied
• Hydroscopic polymer exchange water by direct vapor transfer shall use
molecular transport without the need of condensation
• The ERV core shall be constructed of alternate layers of corrugated
aluminum material and polymeric bactericide dessiccant
impregnated media; and shall not promote growth of mold or bacteria
• The ERV core design shall be made of rectangular utes to provide
very low pressure drop values
Controls
• Choice of low voltage main controls (not included) shall be
energized by ERV unit
• Optional low voltage auxiliary controls (not included) shall be
energized by ERV unit
• Removable terminal block shall be included for quicker low voltage
control connections
• A LED indicator shall indicate defrost selected mode as well as error codes
• ERV unit shall be permanently energized, no control shall be installed
on power supply of unit
Air Flow Balancing
• Unit door shall be equipped with pressure taps as well as a
balancing chart to allow verication of balancing of the ERV unit
• Balancing damper shall be integrated in cold supply and cold
exhaust ports
• Motorized damper shall be integrated in ERV unit, adjacent to the
cold supply port
Defrosting System
• Unit shall allow 3 quick-access defrost modes:
- Standard (factory set regular mode)
- Plus (extended defrost for colder areas)
- Discretion (keeps the same speed when performing defrost as
performing ventilation)
• Unit shall be equipped with Coldshield™ protection to stop air supply
in dwelling if air supply temperature drops below freezing point, due
to abnormal conditions.
Accoustic Noise Power
• The unit shall have a maximum acoustic noise power of 59.3 dBA
on low speed at 0.1 in. w.g. and 69.0 dBA on high speed at 0.4 in. w.g.,
measured at fresh air to building port.
• The unit shall have a maximum acoustic noise power of 49.8 dBA
on low speed at 0.1 in. w.g. and 58.1 dBA on high speed at 0.4 in. w.g.,
measured at exhaust air from building port.
Requirements and standards
• Shall be HVI certied as per CSA C439 Standards
• Shall be ENERGY STAR® qualied
• Shall comply with the UL 1812 requirements regulating
the installation of Energy Recovery Ventilators
• Shall comply with the CSA C22.2 no. 113 Standard
applicable to ventilators
• Shall comply with CSA C444 requirements regulating
the installation of Energy Recovery Ventilators
Warranty
Unit shall be protected by a 5-year warranty on parts only, with the
original proof of purchase.