Broan ErV100 arcHitEctural sPEcifications
AIRFLOW
High static pressure backward blowers shall perform a minimum of
68 CFM @ 1.0 in. w.g.
Optional high speed: 85 CFM
Optional low speed: 65 CFM
CONSTRUCTION
Housing and door shall be made of 22 ga. galvanized steel
Insulation shall be made of one-piece molded expanded polystyrene,
UL 94 HF-1 certied
5" diameter ports shall be made of galvanized steel
Door hinges and latches shall be made of steel
Cold side ports shall have plastic ring to allow vapor barrier sealing
Unit construction and components shall be UL and CSA certied
Unit shall operate all year long without drain
Weight shall not exceed 32 lb.
Fresh air from outside and Exhaust air to outside ports shall be located
on same side
• Backdraft dampers shall be integrated in cold supply and cold
exhaust port
ERV unit shall be HVI certied
MOTORS
Unit shall have two high reliability, external rotor PSC motors, totally
enclosed and thermally protected
The backward blowers shall support high static pressure environment
The insulation class shall be B
FILTERS
ERV unit shall have two washable 20 ppi reticulated polyester
urethane foam lters, UL 900 class 2 certied
Optional MERV 7 lter kit shall be available, part no.: 21030
ERV CORE
The ERV core shall be a crossow aluminum-polymerized paper core,
UL723 certied
Hydroscopic polymer exchange water by direct vapor transfer shall use
molecular transport without the need of condensation
The ERV core shall be constructed of alternate layers of corrugated
aluminum material and polymeric bactericide dessiccant
impregnated media; and shall not promote growth of mold or bacteria
The ERV core design shall be made of rectangular utes to provide
very low pressure drop values
Controls
Unit shall be equipped with an integrated push-button control for
Low or High speed operation
Choice of low voltage main controls (not included) shall be
energized by ERV unit
Optional low voltage auxiliary controls (not included) shall be
energized by ERV unit
Removable terminal block shall be included for quicker low voltage
control connections
A LED indicator shall indicate operating modes as well as error codes
ERV unit shall be permanently energized, no control shall be installed
on power supply of unit
Air Flow Balancing
Unit door shall be equipped with pressure taps as well as a
balancing chart to allow verication of balancing of the ERV unit
• Balancing dampers shall be integrated in cold supply and cold
exhaust ports
Defrost Cycles
Unit operation shall include a choice of regular or extended defrost
cycles, according to climatic conditions
Unit shall be equipped with Coldshield™ protection to stop air supply
in dwelling if air supply temperature drops below freezing point, due
to abnormal conditions.
Accoustic Noise Power
The unit shall have a maximum acoustic noise power of 58.0 dBA
on low speed at 0.1 in. w.g. and 67.8 dBA on high speed at 0.4 in. w.g.,
measured at fresh air to building port.
The unit shall have a maximum acoustic noise power of 49.4 dBA
on low speed at 0.1 in. w.g. and 58.3 dBA on high speed at 0.4 in. w.g.,
measured at exhaust air from building port.
Requirements and standards
Shall be HVI certied as per CSA C439 Standards
Shall comply with the UL 1812 requirements regulating
the installation of Energy Recovery Ventilators
Shall comply with the CSA C22.2 no. 113 Standard
applicable to ventilators
Shall comply with CSA C444 requirements regulating
the installation of Energy Recovery Ventilators
Warranty
Unit shall be protected by a 5-year warranty on parts only, with the
original proof of purchase.