Light Commercial Heat Recovery Ventilators Installation, Operation and Service Instructions VB0002 VB0003 B6LC B1600705 VB0001 B12LC 22638 rev.
Table of Contents 1. Safety Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 2.1 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 2.
2.4 Ductwork 2. Installation The supply and exhaust duct connections on the unit are as follows: 2.1 Inspection UNIT Inspect the exterior of the unit for shipping damage by ensuring that there is no damage to the door, door latches, door hinges, damper, duct collars, cabinet, etc. Inspect the interior of the unit for damage by ensuring that the fan motors and housings, heat exchange core, insulation, dampers, actuators and drain pans are all intact.
2. Installation (cont’d) 3. Controls 2.6 Exterior Hoods 3.1 General Information It is important that the fresh air intake hood be positioned well away from any source of contamination. The exterior supply and exhaust hoods must be separated enough to prevent cross-contamination and at an elevation that will prevent blockage by snow, dirt and leaves. FAN INTERLOCK RELAY OUTPUT (FF) NOTE: SPEED SELECTION (6LC /12LC UNITS ONLY) Consult local building code for restrictions in your area.
3. Controls (cont’d) 5. Maintenance and Service 3.3 Defrost 5.1 Bi-Monthly Maintenance The unit functions are controlled by integrated controls in the unit which may include Exhaust Only Defrost or Recirculation Defrost (via the recirculation module - B6LC and B12LC units only). In cold temperatures, defrost cycles will remove frost from the heat exchanger to maintain good operation.
MOTOR AND BLOWER REMOVAL AND INSTALLATION 5. Maintenance and Service (cont’d) Disconnect power from the unit. To determine if the fan motor is burned out, disconnect the four-wire service connector between the motor and cabinet. Connect the motor directly to a 115 volts power source with an electrical cable, as follows: 5.2 Annual Maintenance ! WARNING Disconnect power before maintaining unit.
6. Service parts 6.1 B6LC-B12LC Exhaust Defrost B C E D F N M G L K I VL0068 Ref. Part No. B SV13036 C D E F G H SV1808139 H J Description Ref. Part No. Description Hinge kit (male-female) SV63336 Autotransformer B6LC - Low Speed Option Core Defrost Actuator B6LC-B12LC SV63340 Autotransformer B12LC - Low Speed Option SV63345 Relay DPDT 120VAC, 1/2 HP, 15A @ 120VAC, B1600705, B6LC, B12LC (Low Speed Opt.
6. Service parts (cont’d) 6.2 B6LC-B12LC Recirculation Defrost B C D E F M L K I J Part No. B SV13036 C D E F G* Description Ref. Hinge kit (male-female) SV1808146 Core Poly UL B6LC-B12LC (unitary) SV1604191 Core Aluminum B6LC-B12LC (unitary) SV201805 Filter SWF 13.125" x 11.25" x 1" (unitary) SV63333 Recirculation Damper B6LC SV63334 Recirculation Damper B12LC SV63335 K* Part No.
6. Service parts (cont’d) 6.3 B1600705 B C D L E K F G I J H VL0070 Ref. Part No. Ref. Part No. B SV16035 Door Latch-Keeper kit H SV13036 Hinge Kit (male-female) I SV1604190 Core Poly UL B1600705 SV225855 Damper Motor Belimo LMB24-3-T, B1600705, B6LC-B12LC (Recirculation Defrost Option) J SV1607456 Drain Fitting B6LC, B12LC, B1600705 (unitary) K SV134147 Filter SWF 18.6" x 15.6" x 1" B1600705 Exhaust (unitary) L SV134145 Filter SWF 19" x 22.
Appendix A MOUNTING DIAGRAMS B6LC AND B12LC UNITS NOTE: Diagrams show standard unit configuration. For units with the reversed door option, the door will be located here.
4.000" 11 28.005" LEFT SIDE B SUPPLY AIR OPENING EXHAUST AIR OPENING 14.000" 10.005" LINE POWER A CONTROL BOX ACCESS LOW VOLTAGE TERMINAL STRIPS 4.028" 5.859" SUPPLY AIR EXHAUST AIR C A 5.125" RETURN AIR OUTDOOR AIR FRONT NOTE: FOR UNITS WITH THE REVERSED DOOR OPTION, INTERIOR COMPONENTS WILL APPEAR AS A MIRROR IMAGE OF THE ABOVE DIAGRAM. 34.000" TOP 19.207" 13.375" D B A B B6LC ALUMINUM CORE Kg PTS LB. 44.21 20.00 A 13.00 B 28.67 26.72 C 58.92 D 17.30 38.21 77.11 TOTAL 170.
3.53" 8.00" 4.00" 12 VK0097A Control Plate 24.50" 8.00" 4.00" 1.75" Control Box Dry Contacts Line Power 2.75" 12.00" A minimum of 12.00" clearance from any obstruction is required for removal of control box. Reverse Door Option Fresh Air to Building Exhaust Air to Outdoors 28.12" 14.00" 5.125" Heat Recovery Core Access Door Drain Fitting Access Door Strap Mounting Location 15.00" Reversed Door Option A minimum of 15.
LEFT SIDE B FRESH AIR TO BUILDING EXHAUST AIR TO OUTDOORS 20.000" 11.325" 4.028" LINE POWER CONTROL BOX ACCESS LOW VOLTAGE TERMINAL STRIPS A 5.715" SUPPLY AIR EXHAUST AIR C 34.000" TOP 5.125" D RETURN AIR OUTDOOR AIR FRONT VIEW NOTE: FOR UNITS WITH THE REVERSED DOOR OPTION, INTERIOR COMPONENTS WILL APPEAR AS A MIRROR IMAGE OF THE ABOVE DIAGRAM. 19.207" 14.250" B ACCESS DOOR 4.000" 2.750" STRAP MOUNT LOCATION A B B12LC ALUMINUM CORE Kg PTS LB. 60.41 27.40 A 19.77 B 43.
VK0099A 3.53" 8.00" 24.50" 4.00" 8.00" 1.75" 41.24" Control Cover Control Box Dry Contacts Line Power 2.75" 14 12.00" A minimum of 12.00" clearance from any obstruction is required for removal of control box. Fresh Air To Building Exhaust Air To Outside 20.00" Reversed Door Option 10.00" 5.125" Heat Recovery Core Access Door Access Door Drain Fitting Strap Mounting Location 15.00" Exhaust Air From Building Fresh Air From Outdoor Reversed Door Option A minimum of 15.
VK0100A 40.500" 8.000" 12.250" 8.000" 3.750" LEFT SIDE 15.250" RETURN AIR OPENING OUTDOOR AIR OPENING 1.875" 14.000" 3.625" RETURN AIR 2.000" OUTDOOR AIR CONDENSATE DRAIN B 2.000" 8.000" 2.000" 10.000" SUPPLY AIR OPENING EXHAUST AIR OPENING 7.500" 8.000" 10.750" 8.000" 1.875" RIGHT SIDE Low Voltage 10.605" Terminal Strips A minimum of 12.00" clearance from any obstruction is required for power hook-up, low voltage remote connection, and control panel access. 12.104" 2.
Appendix C BALANCING DAMPERS POSITION B6LC AND B12LC Reverse Door Option Balancing Damper Min.
Appendix D DRAIN CONNECTIONS B6LC AND B12LC Plastic drain fitting Min. 3” [76 mm] Min. 3” [76 mm] 3/4” NPT coupler Min. 1” [25 mm] Min. 4” [102 mm] Min. 1” [25 mm] To drain NOTES: 1. All hose, pipe and couplers to be supplied by others. 2. Slope drain lines minimum 1/4” per foot. B1600705 Plastic drain fitting Min. 1” [25 mm] To drain 3/4” NPT coupler Min. 4” [102 mm] Min. 3” [76 mm] Min. 4” Min. 1” [102 mm] [25 mm] To drain Copper or plastic pipe Water trap Plastic hose NOTES: 1.
Appendix E TERMINAL CONTROL DIAGRAMS E-1: TERMINAL LABEL E-2: WALL CONTROL CONNECTION A low voltage remote control wiring interface is provided on the unit. The connections for the low voltage remote wiring are located on two terminals adjacent to the exhaust fan outlet (or adjacent to the supply fan outlet on the B1600705 unit). All field installed wiring must be low voltage class II. Two types of remote wall controls are available: 1.
Appendix E (cont’d) TERMINAL CONTROL DIAGRAMS E-4: REMOTE FAN CONTROL E-3: OCCUPIED TIMER/SENSOR CONNECTION (NOT SOLD BY BROAN) Remote fan control can be achieved by connecting dry contact controls to the terminal interface at terminals labeled: LOW - COM - HIGH. Occupancy control is achieved by connection to the terminal interface shown below.
307 283 259 236 212 650 600 550 500 450 20 Supply Air (L/s) 590 566 542 519 495 472 425 377 330 Supply Air (CFM) 1250 1200 1150 1100 1050 1000 900 800 700 B12LC UNIT 189 330 700 400 Supply Air (L/s) Supply Air (CFM) B6LC and B1600705 UNITS 3.2 4.0 5.1 6.3 7.0 7.8 3.9 4.8 5.9 7.2 8.0 8.9 9.7 kW 73°F 5.1 7.0 8.5 9.9 10.7 11.2 12.6 8.1 10.4 12.4 14.1 15.2 15.9 17.4 18.6 9.3 11.7 13.8 15.7 16.9 17.7 19.3 20.6 21.9 kW 73°F 3.7 5.
Appendix H WIRING DIAGRAMS B6LC & B12LC - Exhaust Defrost - Normal Low Speed 1002 BK 1004 BK NEUT CR1024 1 1 2 2 2 2 to 2017 INTAKE R BL NOTE A BN W W 1 1 R 4 2 LOW SPEED GL1004 G 4 4 W NC from 1013 COM DEFROST 1003 PJ1001B BK 4 4 CR1029 W 2 2 PJ1001A BK/Y CR1026 BK/Y 4 2 HIGH SPEED 1 1 BK GN BL 3 3 1021 3 3 1 F 2 1023 I 3 1024 OC 4 from 2007 REMOTE FAN OL 8 6 HIGH SPEED 1009 PJ1007A BK 4 4 from 1022 EXHAUST CR1024 BK 1008 BK PJ1007 BK/Y CR1026 BK/Y BK 100
Appendix H (cont’d) WIRING DIAGRAMS B6LC & B12LC - Exhaust Defrost - Reduced Low Speed 1000 EXT.
Appendix H (cont’d) WIRING DIAGRAMS B6LC & B12LC - Recirculation Defrost - Normal Low Speed W from 1013 NEUT CR1024 BK 2 2 1003 W 1 1 R R 4 2 LOW SPEED GL1004 G W 1 1 R 2 2 BL 3 3 NOTE A GN 3 3 BK 1006 BK 1007 CR1026 BK/Y 8 6 HIGH SPEED PJ1007 BK/Y PJ1007A BK 4 4 4 4 CR1029 W/R 1008 from 1022 COM NC EXHAUST DEFROST CR1024 BK 1009 1011 BK 1012 CAP1007 5 μF BK 1023 I 3 1024 OC 4 1025 OL 1026 2 2 BL BL BL 3 3 NOTE A 3 3 PJ1027 BK 5 5 to 2026 ADDER 120 VAC 7 G 8 B
Appendix H (cont’d) WIRING DIAGRAMS B6LC & B12LC - Recirculation Defrost - Normal Low Speed (cont’d) UNIT CONTROL BOX ADDER CONTROL BOX CONTROL BOX BOM JUMPER SETTINGS FOR CONTROL BOARD JU1 JU1 JU1 JU1 JU1 JU1 JU1 VE0365A A B C D E F G OFF OFF OFF ON ON ON ON TAGS CR1029 CR2022 CR1024 CR1026 CR2028 FU2026 UCB1021 XF2025 24 QTY. 2 DESCRIPTION RELAY SPDT 120 VAC 1 HP 30 A @ 120 VAC 2 RELAY DPST 120 VAC 1 HP 30 A @ 120 VAC 1 1 1 1 RELAY DPDT 24 VAC 1/2 HP 15 A @ 120 VAC FUSE 0.
Appendix H (cont’d) WIRING DIAGRAMS B6LC & B12LC - Recirculation Defrost - Reduced Low Speed 1001 1002 BK W W 4 2 HIGH SPEED BK 4 4 2 2 4 2 LOW SPEED GL1004 G BK W 1 1 R R 2 2 BN MOT1002 SUPPLY BLOWER GN/Y 2 2 BL CAP1001 5 μF BK HIGH COM LOW GND MED W 1 1 R BL 3 3 3 3 1021 F 1 F 2 1023 I 3 1024 OC 4 1022 BK PJ1007 BK/Y PJ1007A BK BN 4 4 4 4 CR1026 BK/Y 8 6 HIGH SPEED CR1029 W/R 1008 from 1022 COM NC EXHAUST DEFROST CR1024 R BK 1009 1 1 R 1 1 R R 2 2 CAP1
Appendix H (cont’d) WIRING DIAGRAMS B6LC & B12LC - Recirculation Defrost - Reduced Low Speed (cont’d) 4 8 12 14 1 5 9 13 UNIT CONTROL BOX ADDER CONTROL BOX FU1015 5 A - B6LC 8 A - B12LC NOTE: AUTOTRANSFORMERS ARE MOUNTED ON THE BACK OF THE CONTROL BOX. B6LC B12LC CONTROL BOX BOM JUMPER SETTINGS FOR CONTROL BOARD JU1 JU1 JU1 JU1 JU1 JU1 JU1 VE0367A A B C D E F G OFF OFF OFF ON ON ON ON TAGS CR1029 CR2022 CR1024 CR1026 CR2028 CR1023 FU2026 UCB1021 XF2025 26 QTY.
Appendix H (cont’d) WIRING DIAGRAMS B1600705 - Recirculation Defrost GD N W R to 1020, 2023 from 1024 120 VAC LOW SPEED from 1025 to 1022, 2024 SUPPLY LOW NEUT GD GN PJ1001 R 1 1 W/Y BN/W LOW COM HIGH GND W 2 2 BK/Y from 1026 HIGH SPEED BK CAP1001 5 μF BK BN GN/Y 4 4 1006 R from 1024 LOW SPEED W/BL from 1021 EXHAUST COM BK/Y from 1026 HIGH SPEED 1007 1008 1009 PJ1007 1 1 CR1029 9 1 DEFROST 1 1 1 2 2 BK/Y BK/Y 12 4 3 3 DEFROST 1 F 1 F 2 1023 I 3 1024 OC 4 1025 OL BN 1026
Appendix H (cont’d) WIRING DIAGRAMS B1600705 - Recirculation Defrost (cont’d) CONTROL BOX BOM 1 5 9 4 8 12 1 5 9 4 8 12 13 14 13 14 TAGS CR1029 CR1030 QTY. FU2023 1 UCB1021 XF2024 R2004 SN1030 TB1001 1 1 1 1 1 2 DESCRIPTION RELAY DPDT 120 VAC 1/2 HP 15 A @ 120 VAC FUSE 0.5 A AND FUSE HOLDER FLUSH MOUNT PC BOARD TRANSFORMER RESISTOR 3.