Spec Sheet
Dimensions anD service clearances: B6lc
28.12" [714]
14" [356]
4" [102]
1.75" [44]
8"
[203]
2.75" [70]
LINE POWER
CONTROL BOX
LOW VOLTAGE
TERMINAL STRIPS
REVERSED DOOR
OPTION
FRESH AIR
TO BUILDING
EXHAUST AIR
TO OUTSIDE
8"
[203]
4"
[102]
24.5"
[622]
3.53"
[90]
LEFT SIDE
19.207" [488]
5.125" [130]
49.55" [1259] (WITH RECIRCULATION MODULE)
NOTE: FOR UNITS WITH THE REVERSED DOOR OPTION, INTERIOR COMPONENTS
WILL APPEAR AS A MIRROR IMAGE OF THE ABOVE DIAGRAM.
FRONT
34" [864]
5.859" [149]
4.028" [102]
ACCESS DOOR
STRAP MOUNTING
LOCATION
DRAIN FITTING
8"
[203]
8"
[203]
14.1"
[358]
14.00"
[356]
FRESH AIR
FROM OUTSIDE
EXHAUST AIR
FROM BUILDING
4"
[102]
1.75"
[44]
RIGHT SIDE
2.75"
[70]
7.705"
[196]
7.1"
[180]
23.5"
[597]
12"
[305]
A MINIMUM OF 12" [305] CLEARANCE FROM ANY OBSTRUCTION
IS REQUIRED FOR REMOVAL OF CONTROL BOX.
CONTROL PLATE
VK0050A
NOTE: Dimensions in brackets are in millimeters.
HRV and ERV
External Static
Pressure
Power
Consumed
Watt
HRV High ERV High Medium Low
in. w.g. Pascal cfm L/s cfm L/s cfm L/s cfm L/s
0.1 25 778 720 340 716 338 660 311 595 281
0.2 50 774 710 335 701 331 646 305 586 276
0.3 75 765 698 329 683 322 632 298 576 272
0.4 100 750 685 323 664 313 617 291 564 266
0.5 125 730 670 316 642 303 600 283 550 259
0.6 150 706 650 307 618 292 580 274 528 249
0.7 175 676 625 295 590 278 547 258 500 236
0.8 200 641 590 278 550 259 505 238 455 215
0.9 225 600 540 255 495 233 450 212 400 189
1.0 250 555 470 222 400 189
Performances
Weight
B6LC Exhaust Defrost B6LC Recirculation Defrost
Core Types Total Assembled Weight
Polypropylene 148 lb.
Aluminum 170 lb.
Polymerized paper 157 lb.
Core Types Total Assembled Weight
Polypropylene 197 lb.
Aluminum 219 lb.
Polymerized paper 206 lb.