The B1600705 is a multi-purpose Heat Recovery Ventilator designed for
the ventilation requirements of residential, commercial and industrial
applications. Utilizing a single element cross-flow core, the B1600705 is
capable of airflows up to 700 cfm (330 l/s) at standard air pressure. Heat
recovery can be matched to the applcation with up to 78% apparent
sensible recovery..
Two metal channels are permanently attached to the bottom of the
case to permit easy installation
High eciency, direct drive, centrifugal blowers
Energy ecient 2-speed PSC motors with sealed ball bearings
Available with FrostBuster™ defrost system
Low voltage control circuit for connection of dehumidistat, switches
or timers
APPLICATIONS INCLUDE:
Swimming Pools Silk Screening Shop
Night Clubs Veterinary Clinics
Fitness Centers Large Residential Homes
Town Halls Art Studios
Commercial Oce Spaces Heath Spas
Many other indoor spaces
WARRANTY
Subject to any applicable consumer protection legislation, Broan
warrants the HRV unit will be free from defective materials and
workmanship for a 2-year period and also provides a 15-year warranty
on the heat exchange core from the manufacturing date, under
normal use, provided that installation is in accordance with the
instructions in the installation manual.
VB0241
Available at:
Controls
Standards Controls
Low voltage control circuit for connection of dehumidistat, switches
or timers.
Terminal block and strain relief bushings are provided for connection
of 115 VAC.
Optional Controls
VT10W remote wall mounted control, providing Off - Intermittent
- Low - Circulation modes. Includes dehumidistat for high speed
control.
Noise and Vibration Control
Fan housing are mounted on special vibration isolators and the fan
mouth is cushioned by an Evazote gasket.
Isolation mounts are supplied for either threaded rod hanging or
oor frame mounting.
VD0072
Circulation
When a VT10W is integrated for control, the circulation mode will
allow high speed circulation through the supply side for as long as
desired. In this mode the exhaust fan is o and the Frostbuster™
damper shuts o the fresh air from outside. This setting may be
useful during warm seasons, or when air conditioning has been
added to the supply ducting.
Defrost
• Broan Frostbuster™ operates a timed cycle of circulation when
outside supply temperature drops below -5°C (23°F).
• Manual circulation is available with the Pool Plus™ wall control.
Positive Shut-Off of Fresh Air
• By setting the optional remote wall control switch to ‘’O, the
outdoor air will be tightly sealed o by the Frostbuster™ damper.
When combined with an exhaust grille with gravity louvers, total
shut-o of outside air during periods of shutdown is possible.
Heat Recovery Core
Easily removable
Material: Non corrosive polypropylene UL94V2 rating
Heat transfer area: 450 ft (42 m)
Maximum exhaust temperature: 150°F (65°C)
Warranty: 15 years
Requirements and Standards
Complies with the CSA C22.2 no. 113 Standard applicable to
ventilators.
Complies with the UL 1812 - ducted Heat Recovery Ventilators.