User manual

Table Of Contents
Section 5: Module Configuration 5-21
Moseley SL9003Q 602-12016 Revision G
5.9.3. Relay Mapping Configuration
5.9.3.1. Mapping Set 1 and “Map Faults-Relays” Set ON
The analog output is selected by connecting pins 17 and 18 to ground pins 19-23 in the
order shown below:
Analog Output:
Ext I/O pin 10
Digital Input
(external I/O connector):
#18 #17 OUTPUT
Open
Open BER
Ground
Open RSL
Open
Ground FWD PWR
Ground
Ground REV PWR
To set the mapping, perform the following steps (refer to section 4.4.10 for
corresponding menu screens):
On the SL9003Q Tx Main Menu
Use Up or Down arrow to select System
<Enter>
Scroll down to Unit-Wide Parameters
<Enter>
Scroll up once then down twice to select Mapping
<Enter>
Use left or right arrow to select setting 0, 1 or 2
<Enter>
<Escape>
<Escape>
Use left or right arrow to select Yes to save settings
<Enter>