Site Sentinel
®
16 Installation and Operation Manual
SETUP
“Email/Network Setup” Web Page – Email Alarm Settings
Email Alarms: Choose Immediate and/or Daily. If Immediate is
selected, then an email will be sent out as soon as an
alarm is generated. If Daily is selected, then each
alarm is queued and the number of queued alarms is
displayed on the Monitor/Control page.
Daily Alarm Email Time: The time that queued alarms are sent. Queued alarms
are sent to the Logging Email Address only.
“Alarm” Recipient Address: Email addresses for up to 8 addresses. These address
correlate to the 8 email addresses selectable on each
I/O Device.
“Email/Network Setup” Web Page – SNMP Manager Settings
SNMP Manager IP Address: This is the IP address of the SNMP manager. The sys-
tem only accepts SNMP requests from this IP address,
and will send traps to this IP address only.
SNMP Manager Trap Port: This is the port number that SNMP trap messages will
be sent.
SNMP Read Community: This is the community name for Read-Only access.
SNMP Write Community: This is the community name for Read-Write access.
SNMP Enable Traps: When checked, trap messages will be sent. When
Unchecked, no trap messages will be sent.
NOTE: A cold-start trap will be sent when the unit boots up if the SNMP
Enable Traps is checked, otherwise trap messages are sent when a device enters
or exits an alarm condition, depending on whether or not alarms are enabled.
“Email/Network Setup” Web Page – NTP Settings
NTP (Time) Server Address: Enter the NTP address here. Default: pool.ntp.org
NTP Port: Normally 123. Default: 123
NTP Update Interval (Min): Time between timing updates. Default: 30
NTP Enabled: Must be enabled for correct timing. Default: Enabled