Site Sentinel
®
16 Installation and Operation Manual
SETUP
Power Failure
Label: Used to identify the monitoring source.
Alarms Enter: This option enables the email alarms if the voltage is no longer
present on this input.
Alarms Exit: This option enables the email alarms when the voltage returns.
Email Addresses: This allows you to configure up to 8 emails to be sent whenever
the input enters or exits an alarm.
Log Device: This enables the email logging of this device.
Delay Time: The delay is in (0 to 999) seconds. This option specifies the wait
time from when a value is out of range before an alarm is acti-
vated.
Alarm LED: User defined color of LED on the Monitor and
Control page when in an alarm condition.
NOTE: After any item has been changed, you MUST press the “Save Settings”
button for your changes to be saved.
Restoring Network Factory Defaults
NOTE: The Site Sentinel® 16 factory defaults may be restored by holding the
“Default” button IN, repowering the unit, wait for the SS and PF LED’s to
flash, then release the “Default” button.