Spec Sheet

CAT.
SCO2B/SCO2LB
ARCHITECTURAL AND ENGINEERING SPEC
TECHNICAL SPECS
SHIPPING SPECS
INSTALLATION OF ALARM
The combination smoke and CO alarm shall be a BRK Model SCO2 and shall provide at a
minimum the following features and functions:
1. An ionization smoke sensing chamber and an electrochemical CO sensor both with a
10 year service life.
2. Powered by a supervised 9V battery (SCO2B uses alkaline, SCO2LB lithium) and
features a solid state piezo horn rated at 85dB at 10 ft. and the unit shall be capable of
self restoring.
3. The unit shall perform self diagnostic tests and issue a malfunction warning (three
chirps) if the unit malfunctions.
4. The unit shall have an “End of Life” signal (5 chirps). This signal should be capable of
temporarily being silenced for up to 2 days. After about 2 days, the signal will resume.
After about 2-3 weeks the signal cannot be silenced.
5. A visual power-on indicator to confirm unit is receiving power. Separate LED ‘s to
indicate a smoke or CO alarm.
6. The CO sensor is adjusted not to detect CO levels below 30 PPM and will not alarm
when exposed to constant levels of 30 PPM for 30 days. It will alarm at the following
levels: 400 PPM CO between 4 and 15 minutes, 150 PPM CO between 10 and 50
minutes and 70 PPM CO between 60 and 240 minutes.
7. Two Latching features: Alarm Latch to easily identify initiating alarm after alarm
condition has subsided. Low battery latch: to visually identify which unit is in low
battery condition. Two Silence Features: Alarm Silence to temporarily silence nuisance
alarms. Low Battery Silence to silence low battery chirp for up to 8 hours.
8. Two Locking features - tamper resistant locking pins that lock battery drawer
and/or alarm to mounting bracket.
9. The unit shall be capable of operating between 40°F (4°C) and 100°F (38°C) and
relative humidity between 10% and 95%.
10. The unit shall contain mounting hardware and shall be listed for wall or ceiling
mounting.
11. The unit shall at a minimum meet the requirements of UL217 and UL2034, CSFM,
NFPA 72 and 720 and the ICC.
Alarm Dimensions: 5.6”dia. x 2.0”H
Weight: 7.6 oz
Operating Voltage: 9V battery powered (alkaline or lithium)
Temperature Range: 40°F (4°C) to 100°F (38°C)
Humidity Range: 10% to 95% relative humidity (RH)
Audio Alarm: 85dB at 10 feet
Test/Silence: Electronically simulates smoke or CO condition,
causing the
unit to alarm. Press and hold test/silence button.
Alarm Reset: Automatic when smoke or CO clears
Smoke Sensor: Dual Ionization
CO Sensor: Electrochemical
Indicator Lights/Sounds:
DC Power: Intermittent Green LED
Local Alarm: Red LED flashes rapidly
Latching Alarm: Red LED flashes 2 sec. on/2 sec. off after local alarm
Low Battery Latch: Green LED flashes on for 2 seconds, off for 2 seconds.
Note: Latching features are active for 15 minutes only.
Listing: Listed to UL217 and UL2034 Standards
Individual Carton Dimensions 5.69”L x 2.25”W x 5.59”H
Weight 0.59 lbs.
Cube 0.04 ft3
UPC 0 29054 00089 7: SCO2B
0 29054 00736 0: SCO2LB
Master Carton Dimensions 14.43”L x 6.19”W x 12.63”H
Master Pack 12
Weight 7.6 lbs.
Cube: 0.65 ft3
I2of5: 200 29054 00089 1: SCO2B
800 29054 00736 6: SCO2LB
Pallet Information
Cases per Layer 19
Number of Layers: 3
Cases per Pallet: 57
Units per Pallet: 684
Cube: 42.2 ft3
Weight: 498 lbs.
©2015 BRK Brands, Inc. a Jarden Corporation
Company (NYSE: JAH)
3901 Liberty Street Road
Aurora, IL 60504-8122
All rights reserved
First Alert is a registered trademark of the First Alert Trust
BRK is a registered trademark of BRK Brands, Inc.
CM3236
brkelectronics.com
Installation of this smoke alarm must conform to NFPA 72. Always check your local
building codes. Follow all instructions for placement as outlined in the user’s manual.
THE PARTS OF THIS SMOKE ALARM
TOP OF ALARM
1. Test/Silence Button
2. Power Light (Green)/Smoke
Alarm light (Red)
3. CO Alarm Light (Red)
4. Battery Drawer
5. Behind Cover: Alarm 85 dB horn
MOUNTING
BRACKET
TOP VIEW SIDE VIEW
5.6”
2.0”
1
2
3
2
5
4
3
BOTTOM OF ALARM
1. Mounting bracket
2. Mounting slots
3. Locking Pins
4. Battery Drawer Latch
5. Battery Drawer - Install
6. 9V battery here
BATTERY DRAWER LOCK
Remove Pin from
Mounting Bracket
Close Door. Insert Pin in Holes
through alarm and Battery Drawer