User guide
22
Commissioning
Commissioning notes for 
Thermostatic Mixing Valves 
The first step in commissioning a 
thermostatic mixing valve is to check the 
following:
1. The designation of the thermostatic 
mixing valve matches the application.
2. The supply pressures are within the 
valves operating range.
3. The supply temperatures are within the 
valves operating range.
4. Isolating valves (and strainers 
preferred) are provided.
If all these conditions are met, proceed to 
set the temperature as stipulated in the 
Maintenance section. 
The mixed water temperature at the 
terminal fitting must never exceed 46˚C.
It is a requirement that all TMV2 approved 
valves shall be verified against the original 
set temperature results once a year. 
When commissioning / testing is due the 
following performance checks shall be 
carried out:
• Measure the mixed water temperature 
at the outlet.
• Carry out the cold water supply isolation 
test by isolating the cold water supply to 
the TMV, wait for five seconds, if water is 
still flowing check that the temperature 
is below 46˚C.
If there is no significant change to the set 
outlet temperature (+/-2˚C or less change 
from the original settings) and the fail-
safe shut off is functioning, then the valve 
is working correctly and no further service 
work is required.
Notes: If there is a residual flow during 
the commissioning or the annual 
verification (cold water supply isolation 
test), then this is acceptable providing the 
temperature of the water seeping from 
the valve is no more than 2˚C above the 
designated maximum mixed water outlet 
temperature setting of the valve.
Temperature readings should be taken at 
the normal flow rate after allowing for the 
system to stabilise.
The sensing part of the thermometer 
probe must be fully submerged in the 
water that is to be tested.
Any TMV that has been adjusted or 
serviced must be re-commissioned 
and re-tested in accordance with the 
instructions in the Maintenance section.
The installation of thermostatic mixing 
valves must comply with the requirements 
of the Water Supply (Water Fittings) 
Regulations 1999.










