Zone Level Information can be communicated for each Module connected to the Operator Interface Panel. The formula below must be used to calculate
the Register Base Address for each Zone.
ZONE LEVEL MODBUS TABLE
ZONE BASE ADDRESS CALCULATION
Zone Offset Examples
OI Registers Zone Base Address Line Count/Zone
1024 1 1024 1 24
2 1048 1
127 4048 1
128 4072 1
1 4096 2
2 4120 2
127 7120 2
128 7144 2
1 47104 16
2 47128 16
127 50128 16
128 50152 16
Zone base addresses = ((line#-1) * 3072) + ((zone#-1) * 24)+1024
TABLE 12: ZONE LEVEL MODBUS TABLE
Name R/W
Modbus Table
Type
Address Notes/Units
Zone
Level
Temperature R Input base address degC * 100
Duty Cycle R Input 1 + base address %
Current R Input 2 + base address A * 1000
Sensor Type R Input 3 + base address
Set Point R/W Holding base address degC * 100
Temp Low Alarm Threshold R/W Holding 1 + base address degC * 100
Temp Caution Alarm Threshold R/W Holding 2 + base address degC * 100
Temp High Alarm Threshold R/W Holding 3 + base address degC * 100
Idle Set Point R/W Holding 4 + base address degC * 100
Idle Temp Low Alarm Threshold R/W Holding 5 + base address degC * 100
Idle Temp High Alarm Threshold R/W Holding 6 + base address degC * 100
Ramp Rate R/W Holding 7 + base address degC * 100 / Minute
Control Type R/W Holding 8 + base address See Control Mode Explanation (Table 2)
Temp Controller Present R Discrete Input base address All others invalid if this is false
Alarming R Discrete Input 1 + base address
Locate Module R/W Coil base address
Idle Mode Enabled R/W Coil 1 + base address
High Temp Alarm R/W Coil 2 + base address Write 0 to attempt unlatch
Low Temp Alarm R/W Coil 3 + base address Write 0 to attempt unlatch
Caution Condition R/W Coil 4 + base address Write 0 to attempt unlatch
Faulty Sensor R/W Coil 5 + base address Write 0 to attempt unlatch
Corrupt Flash Memory R/W Coil 6 + base address Write 0 to attempt unlatch
Overcurrent R/W Coil 7 + base address Write 0 to attempt unlatch
Duty Cycle Low R/W Coil 8 + base address Write 0 to attempt unlatch
Duty Cycle High R/W Coil 9 + base address Write 0 to attempt unlatch
Jacket Problem R/W Coil 10 + base address Write 0 to attempt unlatch
Module Overheat R/W Coil 11 + base address Write 0 to attempt unlatch
Base Overheat R/W Coil 12 + base address Write 0 to attempt unlatch
Unknown Sensor R/W Coil 13 + base address Write 0 to attempt unlatch
Heater Break R/W Coil 14 + base address Write 0 to attempt unlatch
High Temp Alarm Idle R/W Coil 15 + base address Write 0 to attempt unlatch
Low Temp Alarm Idle R/W Coil 16 + base address Write 0 to attempt unlatch