STARTING THE GENERATOR SET
Before starting the generator, the following
procedures should be performed to ensure
peak performance;
Check engine oil level, it should be at or
near the full mark.
Visually inspect engine, generator, and
exhaust system to ensure that they are
free from any obstructions or debris that
may block air flow or possibly ignite from
contact with hot engine components. The
engine compartment should be free of
any objects foreign to its design.
Inspect the battery cables to ensure that
they are tightly connected and free of
corrosion.
Maintain a clean air filter to prevent con-
taminants from entering the engine.
AUTO START
For remote starting, follow the pre-start check-
list, and place the AUTO/OFF-RESET/
MANUAL switch in the auto position. When
the controller receives the start command from
the transfer switch, the starting procedure will
begin. If the generator fails to start, the trans-
fer switch will automatically return to utility
power. Refer to the troubleshooting section of
this manual.
The controller will start the engine if either: 1.)
The control switch is in the MANUAL position
or 2.) The control switch is in the AUTO posi-
tion and the remote start contacts are closed.
Before attempting to start the engine, the
speed input is checked. If it is determined that
the engine is already running, only the fuel
solenoid is energized. Otherwise, the control-
ler will attempt to start the engine by engaging
the fuel solenoid and the starter relay. The
speed input is monitored to determine if the
engine starts.
If the starting speed is detected, the starter
relay is disengaged and normal monitoring is
begun after the startup delay period of 10
seconds. This delay allows oil pressure to be
established and allows the engine speed to
stabilize.
Cranking will continue for 10 seconds if the
engine does not start. After this time, the fuel
solenoid and the starter relay are disengaged
for a rest period of 10 seconds. After the rest
period, another crank attempt is performed.
After five unsuccessful attempts, the controller
will issue an OVERCRANK shutdown fault. If
this occurs follow the guidelines in the trouble-
shooting section of this manual.
MANUAL START
After completing the pre-start checklist, place
the AUTO/OFF-RESET/MANUAL switch in the
manual position. The engine controller will
begin the starting procedure detailed above.
If the generator does not start, return the
switch to the off-reset position for the duration
of 10 seconds and return the switch to the
manual position. If the generator completes a
second starting cycle without successfully
starting, refer to the troubleshooting section of
this manual.
CONTROLLER RESETTING PROCEDURE
The following procedure must be used to reset
the controller, after a fault condition.
1. Place the toggle switch in the OFF/RESET
postion.
2. Switch the circuit breaker to the OFF posi-
tion, and disconnect the load.
3. Correct the fault condition (Refer to fault
shut downs).
4. Place the toggle switch in the MANUAL or
AUTO position for startup.