Specifications

Junction Box
I Inlet Box \
Figure 5. Junction Box Wiring (Typical)
J
10. Connect and secure the wires inside of the junction
box. Refer to Figure 5.
_Pre-wfred from
receptacle to
circuit breakers
Inlet Box
t..==-1
G - Ground
W - Neutral
X - 120 VAC
Y - 120 VAC
TopView _
Pre-wired from
(_) receptacle to
ground connectio_
Grn
FrontView
Figure 6, Inlet Box Wiring (Prewired)
J
11. Connect the ground wire from the junction box to the
Green ground wire (A) in the inlet box (secured to the
front panel of the inlet box) with an appropriate wire
terminal. Refer to Figure 6.
12. Connect the neutral wire to the open receptacle "W"
terminal (B) in the inlet box.
13. Connect the two load wires from the junction box to the
circuit breakers (C) in the inlet box.
14. Install the inlet box inner panel and secure with the
screw removed earlier.
Wiring 120 Volt Circuits:
1. Determine the power circuit in the load center that will
be connected to the "A" circuit breaker in the manual
transfer switch.
CAUTION: When selecting cimuits to wire through the man-
ual transfer switch, DO NOT select circuitswired through a
GFCI in the load center. Wiring a GFCl through the manual
transfer switch will disable the GFCI when generator power
is being used.
A ARNING: Ensure that any selected circuitsthatare part of a multiwire branch circuits are wired on
opposing legs (phases) to prevent inadvertent over-
load of the neutral wire.
F
House Load Center
To Manual Transfer Switch
Figure 7. Load Center Wiring (Typical)