Install Manual
Table Of Contents
Not for
Reproduction
28 BRIGGSandSTRATTON.COM
Generator Specifications (60Hz & 50Hz)
This generator is rated in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) and
CSA (Canadian Standards Association) standard C22.2 No. 100-14 (motors and generators).
Series 29000 Voltage
Rated
Amps *
Frequency
Ambient
Operating Range
Output Sound
Level ^
Shipping
Weight
1-Phase 230 126
50 Hz
-20°F (-28°C)
to 104°F (40°C)
60 dB (3.0L)
66 dB (4.3L)
1831 lbs
(831 kg) (3.0L)
2033 lbs
(922 kg) (4.3L)
1-Phase 120/240 120
3-Phase Wye 115/200 104
3-Phase Wye 220/380 55
3-Phase Wye 230/400 52
3-Phase Wye 240/416 50
Series 35000 Voltage
Rated
Amps *
Frequency
Ambient
Operating Range
Output Sound
Level ^
Shipping
Weight
1-Phase 120/240 145
60 Hz
-20°F (-28°C)
to 104°F (40°C)
61 dB (3.0L)
68 dB (4.3L)
1831 lbs
(831 kg) (3.0L)
2033 lbs
(922 kg) (4.3L)
3-Phase Wye 120/208 121
3-Phase Delta 120/240 105
3-Phase Wye 240/416 61
3-Phase Wye 277/480 53
3-Phase Wye 347/600 42
Series 40000 Voltage
Rated
Amps *
Frequency
Ambient
Operating Range
Output Sound
Level ^
Shipping
Weight
1-Phase 230 174
50 Hz
-20°F (-28°C)
to 104°F (40°C)
66 dB
2033 lbs
(922 kg)
1-Phase 120/240 166
3-Phase Wye 115/200 144
3-Phase Wye 220/380 76
3-Phase Wye 230/400 72
3-Phase Wye 240/416 69
Series 48000 Voltage
Rated
Amps *
Frequency
Ambient
Operating Range
Output Sound
Level ^
Shipping
Weight
1-Phase 120/240 200
60 Hz
-20°F (-28°C)
to 104°F (40°C)
68 dB
2033 lbs
(922 kg)
3-Phase Wye 120/208 167
3-Phase Delta 120/240 144
3-Phase Wye 240/416 83
3-Phase Wye 277/480 72
3-Phase Wye 347/600 58
Series 50000 Voltage
Rated
Amps *
Frequency
Ambient
Operating Range
Output Sound
Level ^
Shipping
Weight
1-Phase 230 217
50 Hz
-20°F (-28°C)
to 104°F (40°C)
67 dB
2419 lbs
(1097 kg)
1-Phase 120/240 208
3-Phase Wye 220/380 95
3-Phase Wye 230/400 90
3-Phase Wye 240/416 87
Series 60000 Voltage
Rated
Amps *
Frequency
Ambient
Operating Range
Output Sound
Level ^
Shipping
Weight
1-Phase 120/240 250
60 Hz
-20°F (-28°C)
to 104°F (40°C)
70 dB
2419 lbs
(1097 kg)
3-Phase Wye 120/208 215
3-Phase Delta 120/240 186
3-Phase Wye 240/416 108
3-Phase Wye 277/480 93
3-Phase Wye 347/600 75
* Natural gas (NG) rating will depend on specific fuel but typical derates are 10 to 20% lower than Propane.
^ Per ISO 3744. Lowest mic at 23 feet (7 meters) at no load.