Final Installation Considerations
Installation Inspection
Before placing the generator system into service, review the
instructions while carefully inspecting the entire installation
to ensure the installation is complete and correct.
Fuel Supply System
Make sure that all fuel pipe connections are tight, secure,
and without leaks. Make sure that all fuel line shutoff valves
are OPEN and that adequate fuel pressure is available.
Battery
The installer must supply and install a starting battery that
conforms to the specifications listed below.
Battery Specifications
Volts 12 Volt DC
Amps (MIN) 775 CCA (cold cranking amps)
Type AGM (Absorbent Glass Mat)
BCI Group Size 34
Install the battery as described under Servicing the
Battery in the Maintenance section. Always make sure the
NEGATIVE cable is connected last.
WARNING
Storage batteries give off explosive hydrogen
gas during recharging.
Slightest spark will ignite hydrogen
and cause explosion, resulting in death, serious injury and/
or property damage. Battery electrolyte fluid contains acid
and is extremely caustic. Contact with battery contents
could cause severe chemical burns. A battery presents a
risk of electrical shock and high short circuit current.
• DO NOT dispose of battery in a fire. Recycle battery.
• DO NOT allow any open flame, spark, heat, or lit
cigarette during and for several minutes after charging
a battery.
• DO NOT open or mutilate the battery.
• Wear protective goggles, rubber apron, rubber boots
and rubber gloves.
• Remove watches, rings, or other metal objects.
• Use tools having insulated handles.