Install Manual

Not for
Reproduction
17
Power Connections
Compare this illustration with the generator to familiarize yourself with the location of these connections.
B
C
A A
A - Power Connection - Power connection to transfer switch.
B - Neutral Connection - Connect to transfer switch neutral.
C - Ground Connection - Connect to transfer switch ground.
Ground the generator per applicable codes, standards, and
regulations. There are two generator GND lug locations.
The location shown by (C, above) should suffice for most
applications. The second generator GND lug is located on the
frame. This should ONLY be used for a ground rod located at
the generator, if required by local codes.
For system connections such as remote start, e-stops, and
controller inputs and outputs, refer to the connection diagrams
on the following pages.
For power output connection, use 75°C (167°F) wire
rated for ambient temperature of 40°C (104°F) per NEC
Tables 310.15(B)(16) and 310.15(B)(2)(a).
For utility circuit connection, use #14 AWG minimum 600
volt, 167-194°F (75-90°C) wire.
For transfer switch communication, use #18 AWG
twisted pair conductors, no greater than 200 ft (60 m) in
length, 600 volt, 167-194°F (75-90°C) wire.