Spec Sheet

35kW
¹
STANDBY GENERATOR
55
Briggs & Stratton Corp. reserves the right to make changes in specifications and features shown herein, or discontinue the product described at any time without notice or obligation.
BRIGGS&ST R AT TO N
POST OFFICE BOX 702
MILWAUKEE, WI 53201 USA
Copyright ©2016. All rights reserved. BS1007-L – 8/16
Disclaimer: Not for Prime Power or use where standby systems are legally required, for serious
life safety or health hazards, or where lack of power hampers rescue of fire-fighting operations.
FUEL PIPE SIZE RECOMMENDATION CHART (CAPACITY IN THOUSANDS OF BTU/HOUR)
Natural Gas / Inlet Pressure less than 2 PSI / Pressure Drop 1/2” Water Column / Specic Gravity 0.60
1/2" pipe capacity 3/4" pipe capacity 1" pipe capacity 1-1/4" pipe capacity 1-1/2" pipe capacity 2" pipe capacity
20' Length
*
118 247 466 957 1,43 0 2,760
40' Length
*
81 170 320 657 985 1,9 0 0
60' Length
*
65 137 257 528 791 1,5 20
80' Length
*
56 117 220 452 677 1,3 0 0
100' Length
*
50 104 195 400 600 1,16 0
Liquid Propane / Inlet Pressure 11” Water Column / Pressure Drop 1/2” Water Column / Specic Gravity 1.50
1/2" pipe capacity 3/4" pipe capacity 1" pipe capacity 1-1/4" pipe capacity 1-1/2" pipe capacity 2" pipe capacity
20' Length
*
200 418 788 1,617 2,423 4,666
40' Length
*
137 287 541 1,111 1,66 5 3,207
60' Length
*
110 231 435 892 1,3 37 2,575
80' Length
*
101 212 400 821 1,23 0 2,370
100' Length
*
101 212 400 821 1,23 0 2,370
*Total length of piping from outlet of regulator to appliance furthest away.
SUPPORT EVERY STEP
OF THE WAY
NEED HELP? Just call 800-759-2744
Our technical support team is trained to answer
questions on our generators, transfer switches
and accessories.
CALL TODAY FOR A FREE
IN-HOME ESTIMATE!
800-743- 4115
¹ This generator is rated in accordance with UL (Underwriters Laboratories) 2200
(stationary engine generator assemblies) and CSA (Canadian Standards Association)
standard C22.2 No. 100-14 (motors and generators).