Spec Sheet

35kW
¹
STANDBY GENERATOR
2
LUBRICATION
Oil Capacity (qts / ltrs)
4.5 / 4.3
Oil Capacity with Filter
(qts / ltr)
5.0 / 4.7
Oil Filter (quantity / type)
1 / Spin-on
Lubrication System
Full Pressure
Recommended Oil
API GF-4 10W30
ALTERNATOR SPECS
Type
4-Pole, Rotating Field
Voltage Regulator
Solid State, Volts / Hz
Insulation (rating)
Class H
Designed Temperature Rise Limit
125°C
Bearing (quantity / type)
1 / Sealed
Voltage Reg NL to FL
+ / -1.0%
Frequency Compensation
8V / Hz Voltage Drop Below 55 Hz
ENGINE FUEL SYSTEM SPECIFICATIONS
Recommended Fuel
LP min LHV (btu / ft
3
)
NG min LHV (btu / ft
3
)
2260
890
Fuel Supply Pressure (in-H
2
0)
7-11 (at full load)
Fuel Supply Line at Engine (npt)
1”
ENGINE
Engine Model
4.3L
Industrial Powertrain
Engine Type
6 Cylinder, 4-Cycle
Engine Speed (RPM) 180 0
Engine Fuel
Liquid Propane Vapor (LPV)
or Natural Gas (NG)
Induction System
Naturally Aspirated
Air Filter Type
Dry
Displacement (ltr / cc)
4.3 / 4294
Freq Reg NL to FL
Isochronous
Block Heater
Included
Governor Type
Electronic
Frequency Regulation
+ / -.5%
Starter Motor Rated Voltage
12 Vo l t
Battery (volts dc / cca)
12 Volt / 775
ENGINE OUTPUT DERATINGS - STANDBY
Rated Temp
104°F / 40°C
Rated Altitude
Sea Level
Max Altitude
15,000 ft
Temperature Derate
1% for each 10°F (5.6°C) above
rated temp
Altitude Derate
3% / 1000 ft
ENGINE SPECIFICATIONS
FUEL CONSUMPTION
3
50% Load 100% Load
Liquid Propane 102 f t
3
/ hr 2.8 gal / hr 160 f t
3
/ hr 4.4 gal / hr
Natural Gas 253 ft
3
/ hr 253,000 btu / hr 394 ft
3
/ hr 394,000 btu / hr
SOUND RATING
AT 7 METERS PER ISO 3744
67 dBA
Lowest measurement of 12 microphones around generator.
Sound level measurement at other locations around generator
may be different depending upon installation configuration.
OPERATIONS
¹ This generator is rated in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies)
and CSA (Canadian Standards Association) standard C22.2 No. 100-14 (motors and generators).
3
Fuel consumption rates are estimated based on normal operating conditions. Generator operation may be greatly affected by
elevation and the cycling operation of multiple electrical appliances – fuel flow rates may vary depending on these factors.