Dimensions Guide
17 & 20kW
¹
 Standby Generator
3
Lubrication
Oil Capacity (L / qt) 2.3 / 2.46
Lubrication System Full Pressure
Recommended Oil 5W30 Full Synthetic
Alternator Specs
Manufacturer Briggs & Stratton
Type Self-Excited, 4-Lead
Voltage Regulator Automatic
Insulation Class F
Controller Features
Generator Sensing Single phase voltage monitoring
LCD Display Displays multi-line text and graphics
Fault Display Provides additional data regarding fault
Exercise Cycle
Default: Start and run for 16 seconds; 
Abort exercise below 40° F (internal 
temperature)
Power Save Mode Reduces power consumption
Operations
Engine Specifications
Sound Rating At 7 Meters
64 dBA
4
Fuel Consumption
2
Full Load 1/2 Load No Load
17kW
1
BTU / hr
NG - 218,000
LPV - 239,000
NG - 150,000
LPV - 152,000
NG - 92,000
LPV - 72,000
ft
3 
/ hr
NG - 219
LPV - 99
NG - 152
LPV - 64
NG - 95.3
LPV - 32
m
3 
/ hr
NG - 6.2
LPV - 2.8
NG - 4.3
LPV - 1.8
NG - 2.7
LPV - 0.9
g
/ hr LPV - 2.7 LPV - 1.7 LPV - 0.8
Full Load 1/2 Load No Load
20kW
1
BTU / hr
NG - 218,000
LPV - 239,000
NG - 150,000
LPV - 152,000
NG - 92,000
LPV - 72,000
ft
3 
/ hr
NG - 219
LPV - 99
NG - 152
LPV - 64
NG - 95.3
LPV - 32
m
3 
/ hr
NG - 6.2
LPV - 2.8
NG - 4.3
LPV - 1.8
NG - 2.7
LPV - 1.13
g
/ hr LPV - 2.7 LPV - 1.7 LPV - 0.8
Unlike some other standby generator 
manufacturers, our warranty covers parts, 
labor AND travel for the full length of the 
warranty with no start-up costs!
1
  This generator is certified in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) and CSA (Canadian Standards Association) standard C22.2 No. 100-14 (motors and generators).
2
 Fuel consumption rates are estimated based on normal operating conditions at ½ load. Generator operation may be greatly affected by elevation and the cycling 
operation of multiple electrical appliances – fuel flow rates may vary depending on these factors.
3
 See operator’s manual or BRIGGSandSTRATTON.com for complete warranty details.
4
 Lowest no-load measurement per ISO 3744. Sound level measurement at other locations around generator may be different depending upon installation configuration
.
Engine
Engine Brand Vanguard
Engine Speed (RPM) 3600
Engine Fuel
Liquid Propane Vapor (LPV) or 
Natural Gas (NG)
Engine Cylinder Configuration OHV
Number of Cylinders 2
Displacement (L / Ci) 0.993 / 60.60
Compression Ratio 9:7:1
Governor Type Electronic
Frequency Regulation +/- 0.3 Hz (0.5%)
Valves OHV with Hardened Seats
Ignition System
Fixed Timing Magnetron®  
Electric Ignition 
Starter Motor Rating Voltage 12 Volt
Battery Required
12 Volt, Group BCI 24, 
500 CCA Minimum
Peak Motor Starting kVA
17kW - 39 
20kW - 41