Installation
This product is only for use as an optional generator system
which provides an alternate source of electric power
and to serve loads such as heating, refrigeration, and
communication systems that, when stopped during any power
outage, can cause discomfort or inconvenience.
Every effort has been made to make sure that the information
in this manual is accurate and current. However, we reserve
the right to change, alter, or otherwise improve the product
and this document at any time without prior notice.
Only current licensed electrical and plumbing professionals
can attempt generator system installations. Installations must
strictly comply with all applicable codes, industry standards,
laws and regulations.
Lifting the Generator
 WARNING
Hazardous Voltage - Contact with power lines could
cause electric shock or burns, resulting in death or serious
injury.
• If lifting or hoisting equipment is used, DO NOT contact
any power lines.
• DO NOT lift or move generator without assistance.
Proper tools, equipment, and qualified personnel must be
used in all phases of handling and moving the generator. The
approximate weight of the generator is listed in theGenerator
Specificationssection.
Use the lifting holes (A) in the base of the generator to lift
the generator onto the concrete pad. Lift the generator in
accordance with OSHA or local lifting regulations. Retouch
any chipped paint with the supplied touch-up paint.
Cold Weather Kit
If the generator operates in temperatures below 30°F (-1°C),
it is HIGHLY RECOMMENDED that a Cold Weather Kit be
installed.
Cold Weather Kit, Part No. 6578 (Fortress models) includes:
• Battery warmer
• Battery stand
Cold Weather Kit, Part No. 6567 (Briggs & Stratton models)
includes:
• Oil warmer
• Battery warmer
• Battery stand
• Wire harness
These items are available at your local service dealer.
If you need more information, please
call800-732-2989between 8:00 AM and 5:00 PM CT.
Anchoring and Wind Rating
Concrete Anchoring of Unit to Poured or
Existing Slab
To achieve the listed wind rating, the generator must be
installed in strict compliance with this installation manual.
The product components must be of the material specified
and all screws must be installed in accordance with the
applicable provisions and the anchor manufacturer’s
published installation instructions.
The concrete slab/pad must meet the requirements below
and the generator must be anchored with the anchors
ofAnchor Types1 or 2.
Anchor Types
1. Qty (4) 3/8” SS ITW RED HEAD LDT, Anchor embedded
2 ½” (63.5mm) in 3000 psi concrete. 3” (76.2mm) from
the edge minimum, 6” (152.4mm) spacing minimum.
Not for 