Installation Guide
15
2. Qty (4) 3/8” SS Powers/Dewalt Power Stud +SD2
Anchor embedded 2 ½” (63.5mm) in 3000 psi concrete.
3” (76.2mm) from the edge minimum, 6” (152.4mm)
spacing minimum.
There are four 7/16” hole locations (A) in the base of the
generator in which to anchor the unit.
Concrete Slab/Pad Types
PAD DIMENSIONSWIND
RATING
MPH
PAD
MODEL
Width Length Thickness
CONCRETE
SPEC
Up to 140 Pre-cast
Pad
(contact
dealer)
37in
(939.8mm)
54.4in
(1381.8mm)
3in
(76.2mm)
3000 PSI
140 to 175 Pre-cast
Pad
(contact
dealer)
37in
(939.8mm)
54.4in
(1381.8mm)
4in
(101.6mm)
3000 PSI
140 to 175 Poured 38in
(965.2mm)
55in
(1397mm)
5in
(127mm)
3000 PSI
These items are available at your local service dealer.
NOTICE Unless mandated by local or state codes, or
required to achieve wind rating, a concrete slab/pad is not
required
Electrical and Fuel Inlet Locations
The 3/4 inch N.P.T. fuel inlet connector (A) and electrical inlet
locations (B) are shown below.
A ½ inch knock-out is provided for the electrical inlet. This
inlet may be enlarged or supplemented to accommodate a
maximum conduit size of 1-½ inches. Make sure that the
installed conduit(s) enter the unit in zone (C) as shown in the
drawing below so that they properly enter the electrical box
and do not interfere with the fully opened roof.
Access Panels
The generator enclosure has several access panels, as
shown.
The access panels and the components located behind them
are listed below:
(A) Roof (Control Panel, air filter, oil dipstick, and circuit
breaker)
(C) Rear Access Panel (fuel regulator, fuel selector, and
engine starter)
(D) Control Panel Cover (field wiring and control wires)
(F) Battery Panel (battery and generator data label)
(H) Front Access Panel (oil drain and oil filter)