Installation Guide
18
Instructions GC1031 GENSET Controller Manual,"
PN:80086364.
22. Close the roof.
23. Restore utility power to generator.
24. Push the control board AUTO button.
Electrical Field Connections
WARNING
Generator voltage could cause electrical shock or burn resulting in death or serious injury.
• Installation must be performed by a licensed professional.
• Disconnect all sources of electricity before installing or servicing equipment.
• Ground system before applying power.
WARNING
Hazardous Voltage -Installing low and high voltage wire in same conduit could cause electric shock or burns,
resulting in death or serious injury.
• Do not run low and high voltage wire in the same conduit unless the insulation rating on ALL wiring is rated for 600V.
See NFPA 70 for more information.
Low Voltage connections are made via a field connections terminal block (E) in main electrical area. Compare this illustration
with your generator to familiarize yourself with the location of these connections.
Legend for System Connector Location
(A)Two Pin Terminal Block — Used to connect utility 240 VAC from fuse block in ATS to the control board. Connect only one
wire per terminal. Use #14 [2.5mm2] AWG minimum 300 volt wire.
(B) Transfer Switch Connection — Controls transfer switch contactor.
(C) 2-wire start—Used for optional remote start contact.
(D) E-Stop—For use with with optional external E-stop.
(E) Field Connections Terminal Block—Reference the table that follows.