Installation Guide

19
(F)Power Connection (L1 and L2) — Power connection to transfer switch.
(G)Ground Connection — Connect to transfer switch ground wire.
(H)Neutral Connection — Connect to transfer switch neutral wire.
(J) Communications Terminal Block— Reference the table that follows.
Pin Number Description Wire type Connect To Notes
1 12VDC 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
Transfer switch basic
controller J7-8 12VDC
2 GND 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
Transfer switch basic
controller J7-7 GND
3 Transfer Signal 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
Transfer switch basic
controller J7-4 T/R
Transfer switch Transfer
Signal (only works with basic
Transfer Switch Controller).
4 2Wire-Start 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
5 2Wire-Start 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
Refer to Transfer switch
manual to verify if this function
is available.
Contact Close for
Genset Start.(Only for
transferswitch that provides
this option)
Mains monitoring must be
disabled in the controller.
6 E-Stop 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
E-Stop Switch
7 E-Stop 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
E-Stop Switch
Contact Open to Shutdown
Genset
8 Not Used
9 12VDC 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
10 (B) 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
11 (A) 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
12 GND 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
Refer to the Amplify Gateway
Manual.
Comm to WIFI module
13 12VDC 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
14 (B) 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
15 (A) 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
16 GND 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
Refer to the InfoHub™
Premium Manual.
Comm to Cellular module
25 Utility 14AWG [2.5mm
2
] 300V
minimum, 90°C Cu Wire
Transfer switch Utility
26 Utility 14AWG [2.5mm
2
] 300V
minimum, 90°C Cu Wire
Transfer switch Utility
Voltage Sensing for Genset
Start. Use either this signal or
2-wire start signal for Genset
Start Signal.
For power output connection (L1, L2, Neutral (N), and Ground), refer to the National Electric and local codes.
For communication wires use #18 AWG [1mm
2
] twisted pair conductors, no greater than 500 ft in length, 300 volt wire.
When connecting to the terminal block, fasten only one wire to each connector screw.
Torque terminal block screws to 4.4 in-lb [0.49 Newton meter].
Not for
Reproduction