Specification Sheet
17 & 20kW
¹
Standby Generator
3
Lubrication
Oil Capacity (L / qt) 2.3 / 2.46
Low Pressure Switch Included
Lubrication System Full Pressure
Oil Briggs & Stratton 5W30 Full Synthetic
Alternator Specs
Manufacturer Briggs & Stratton
Type Self-Excited, 4-Lead
Voltage Regulator Automatic
Insulation Class F
Peak Motor Starting kVA 17kW - 39 / 20kW - 41
Controller Features
Generator Sensing Single phase voltage monitoring
LCD Display Displays multi-line text and graphics
Fault Display Provides up to 39 detailed fault codes
Exercise Cycle
Six exercise length options
Default: Start and run for 16 seconds;
Abort exercise below 40° F (internal
temperature)
Operations
Engine Specifications
Fuel Consumption
2
Full Load 1/2 Load No Load
17kW
1
BTU / hr
NG - 248,000
LPV - 295,000
NG - 170,000
LPV - 185,000
NG - 99,000
LPV - 72,000
ft
3
/ hr
NG - 248
LPV - 118
NG - 170
LPV - 74
NG - 99
LPV - 40
m
3
/ hr
NG - 7.02
LPV - 3.34
NG - 4.81
LPV - 2.10
NG - 2.80
LPV - 1.13
g
/ hr LPV - 3.19 LPV - 2.00 LPV - 1.08
Full Load 1/2 Load No Load
20kW
1
BTU / hr
NG - 260,000
LPV - 337,500
NG - 187,000
LPV - 207,500
NG - 99,000
LPV - 100,000
ft
3
/ hr
NG - 260
LPV - 135
NG - 187
LPV - 83
NG - 99
LPV - 40
m
3
/ hr
NG - 7.36
LPV - 3.82
NG - 5.30
LPV - 2.35
NG - 2.80
LPV - 1.13
g
/ hr LPV - 3.65 LPV - 2.24 LPV - 1.08
Unlike some other standby generator
manufacturers, our warranty covers parts,
labor AND travel for the full length of the
warranty with no start-up costs!
1
This generator is certified in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) and CSA (Canadian Standards Association) standard C22.2 No. 100-14 (motors and generators).
2
Fuel consumption rates are estimated based on normal operating conditions at ½ load. Generator operation may be greatly affected by elevation and the cycling
operation of multiple electrical appliances – fuel flow rates may vary depending on these factors.
3
See operator’s manual or BRIGGSandSTRATTON.com for complete warranty details.
4
Lowest no-load measurement per ISO 3744. Sound level measurement at other locations around generator may be different depending upon installation configuration
.
Engine
Engine Brand Vanguard
Engine Speed (RPM) 3600
Engine Fuel
Liquid Propane Vapor (LPV) or
Natural Gas (NG)
Engine Cylinder Configuration OHV
Number of Cylinders 2
Displacement (L / Ci) 0.993 / 60.60
Compression Ratio 9:7:1
Governor Type Electronic
Frequency Regulation +/- 0.3 Hz (0.5%)
Valves OHV with Hardened Seats
Ignition System
Fixed Timing Magnetron®
Electric Ignition
Starter Motor Rating Voltage 12 Volt
Battery Required
12 Volt, Group BCI 26 or 51,
540 CCA Minimum
High Temperature Switch Included
Dura-Bore Cast Iron
Cylinder Sleeve
Included
Sound Rating At 7 Meters
Low Idle Mode 64 dBA
4
No Load 67 dBA
4