Installation Guide
19
(F)Power Connection (L1 and L2) — Power connection to transfer switch.
(G)Ground Connection — Connect to transfer switch ground wire.
(H)Neutral Connection — Connect to transfer switch neutral wire.
(J) Communications Terminal Block— Reference the table that follows.
Pin Number Description Wire type Connect To Notes
1 12VDC 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
Transfer switch basic
controller J7-8 12VDC
2 GND 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
Transfer switch basic
controller J7-7 GND
3 Transfer Signal 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
Transfer switch basic
controller J7-4 T/R
Transfer switch Transfer
Signal (only works with basic
Transfer Switch Controller).
4 2Wire-Start 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
5 2Wire-Start 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
Refer to Transfer switch
manual to verify if this function
is available.
Contact Close for
Genset Start.(Only for
transferswitch that provides
this option)
Mains monitoring must be
disabled in the controller.
6 E-Stop 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
E-Stop Switch
7 E-Stop 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
E-Stop Switch
Contact Open to Shutdown
Genset
8 Not Used
9 12VDC 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
10 (B) 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
11 (A) 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
12 GND 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
Refer to the Amplify Gateway
Manual.
Comm to WIFI module
13 12VDC 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
14 (B) 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
15 (A) 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
16 GND 18AWG[1mm
2
] twisted pair
conductors, 300V minimum,
90°C Cu wire.
Refer to the InfoHub™
Premium Manual.
Comm to Cellular module
25 Utility 14AWG [2.5mm
2
] 300V
minimum, 90°C Cu Wire
Transfer switch Utility
26 Utility 14AWG [2.5mm
2
] 300V
minimum, 90°C Cu Wire
Transfer switch Utility
Voltage Sensing for Genset
Start. Use either this signal or
2-wire start signal for Genset
Start Signal.
• For power output connection (L1, L2, Neutral (N), and Ground), refer to the National Electric and local codes.
• For communication wires use #18 AWG [1mm
2
] twisted pair conductors, no greater than 500 ft in length, 300 volt wire.
• When connecting to the terminal block, fasten only one wire to each connector screw.
• Torque terminal block screws to 4.4 in-lb [0.49 Newton meter].