Specification

17&20kW STANDBY GENERATOR
2
FUEL CONSUMPTION
1
50% Load 100% Load
17kW
Liquid Propane 74 f t
3
/ hr 2.06 gal / hr 118 f t
3
/ hr 3.28 gal / hr
Natural Gas 170 f t
3
/ hr 248 ft
3
/ hr
20kW
Liquid Propane 83 ft
3
/ hr 2.31 gal / hr 135 f t
3
/ hr 3.75 gal / hr
Natural Gas 187 f t
3
/ hr 260 ft
3
/ hr
SOUND RATING
AT 7 METERS PER ISO 3744
17kW 20kW
69 dBA 68.4 dBA
Lowest measurement of 12 microphones around
generator. Sound level measurement at other locations
around generator may be different depending upon
installation configuration.
LUBRICATION
Oil Capacity (oz) 79
Lubrication System Full Pressure
Recommended Oil 5W30 Full Synthetic
Low Oil Pressure Sensor Yes
ALTERNATOR SPECS
Manufacturer Briggs & Stratton
Type Self-Excited, Rotation Field
Voltage Regulator Automatic
Insulation Class F
CONTROLLER FEATURES
Hour Meter Yes
LED Digital Display Yes
Fault Code Display Yes
Weekly Exerciser Yes
ENGINE
Engine Model Briggs & Stratton Vanguard
Engine Model Type Trim Number 613275-0003-E1
Engine Speed (RPM) 3600
Engine Fuel
Liquid Propane (LP) or
Natural Gas (NG)
Engine Cylinder Configuration OHV
Number of Cylinders 2
Displacement (cc) 60.6 / 993
Bore & Stroke (in) 3.37 / 3.41
Compression Ratio 8.5:1
Governor Type Electronic
Frequency Regulation +/- .5%
Valves OHV with Hardened Seats
Ignition System
Fixed timing Magnetron
®
Electric Ignition
Starter Motor Rating Voltage 12 Vo l t
Battery 12 Vo l t
OPERATIONS
ENGINE SPECIFICATIONS
1
Fuel consumption rates are estimated based on normal operating conditions. Generator operation may be greatly affected by
elevation and the cycling operation of multiple electrical appliances – fuel flow rates may vary depending on these factors.