Dimensions Guide
17 & 20kW
¹
Standby Generator
3
Lubrication
Oil Capacity (oz) 78
Lubrication System Full Pressure
Recommended Oil 5W30 Full Synthetic
Alternator Specs
Manufacturer Briggs & Stratton
Type Self-Excited, Rotation Field
Voltage Regulator Brushed/Electronic
Insulation Class F
Controller Features
Hour Meter Yes
LED Digital Display Yes
Fault Code Display Yes
Weekly Exerciser Yes
Low Oil Pressure Shutdown Yes
High Temperature Shutdown Yes
Engine
Engine Brand Vanguard®
Engine Speed (RPM) 3600
Engine Fuel
Liquid Propane Vapor (LPV) or
Natural Gas (NG)
Engine Cylinder Configuration OHV
Number of Cylinders 2
Displacement (cc) 993
Compression Ratio 8.5:1
Governor Type Electronic
Frequency Regulation +/- 1 Hz
Valves OHV with Hardened Seats
Ignition System
Fixed Timing Magnetron
Electric Ignition
Starter Motor Rating Voltage 12 Volt
Battery Required
12 Volt, Group BCI 26 or 51,
540 CCA Minimum
Operations
Engine Specifications
Sound Rating At 7 Meters
64 dBA
4
Fuel Consumption
2
Full Load 1/2 Load No Load
17kW
BTU/hr
NG - 248,000
LPV - 295,000
NG - 170,000
LPV - 185,000
NG - 99,000
LPV - 100,000
ft
3
/hr
NG - 248
LPV - 118
NG - 170
LPV - 74
NG - 99
LPV - 40
m
3
/hr
NG - 7.02
LPV - 3.34
NG - 4.81
LPV - 2.10
NG - 2.80
LPV - 1.13
Full Load 1/2 Load No Load
20kW
BTU/hr
NG - 260,000
LPV - 337,500
NG - 187,000
LPV - 207,500
NG - 99,000
LPV - 100,000
ft
3
/hr
NG - 260
LPV - 135
NG - 187
LPV - 83
NG - 99
LPV - 40
m
3
/hr
NG - 7.36
LPV - 3.82
NG - 5.30
LPV - 2.35
NG - 2.80
LPV - 1.13
Unlike other standby generator manufacturers,
our warranty covers parts, labor AND travel
for the full length of the warranty with no
start-up costs!
1
This generator is certified in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) and CSA (Canadian Standards Association) standard C22.2 No. 100-14 (motors and generators).
2
Fuel consumption rates are estimated based on normal operating conditions at ½ load. Generator operation may be greatly affected by elevation and the cycling
operation of multiple electrical appliances – fuel flow rates may vary depending on these factors.
3
See operator’s manual or BRIGGSandSTRATTON.com for complete warranty details.
4
Lowest no-load measurement per ISO 3744. Sound level measurement at other locations around generator may be different depending upon installation configuration
.