Submittal Sheet

S2-2
Hot Water, Chilled Water, 50/50 Glycol Solutions
Valve Body Pressure/
Temperature Rating
Technical Specifications
Service
Rangeability
Maximum Recommended
Operating Pressure Drop
50 PSI Maximum Differential Pressure for Valves with Characterized
Flow Control Disk and 30 PSI Maximum for Quiet Service Ball Valves
Greater than 500:1
Leakage
NPT or BSP
Stem
Seats
Materials
300 Series Stainless Steel
Graphite-Reinforced PTFE with EPDM O-Ring backing
Body
Ball
EPDM Double O-Rings
Disclaimer - The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond
these specifications, consult the local Bray office. Bray, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
Forged Brass
300 Series Stainless Steel
Characterizing
Disk
Stem Seals
Amodel®
See Actuator Specifications
Minimum Ambient Operating
End Connections
Compliance CRN
.01% of Maximum Flow per ANSI/FCI 70-2, Class 4
1% of Maximum Flow for Three-Way Bypass Port
15 PSIG (103 kPa) Saturated Steam for HVAC Systems
Cold Working Pressure (CWP) 580 PSI (PN 40)
Water (with Standard Mounting) -22˚F to 203˚F (-30˚C to 95˚C)
Water (with “High Temp” Mounting) -22˚F to 284˚F (-30˚C to 140˚C)
Steam (with “High Temp” Mounting) 15 PSIG (103 kPa) at 284˚F (140˚C)
Flow Characteristics
Two-Way Equal Percentage
Three-Way Equal Percentage Port A, Linear Port B (Bypass)
OC16910.5
Close-Off 200 PSI
Warranty 5 Years limited from time of shipment.
SoftTouch 2 - Specifications
www.braycommercialdivision.com
13788 West Road, Suite 200A
Houston, Texas 77041
BCDSales@Bray.com
Phone: 1-888-412-2729
S2-2