BRAY Series 70 Servo Pro
Operation and Maintenance Manual
BRAY Series 70 Servo Pro
Operation and Maintenance Manual
Problem Possible Cause Possible Solutions
Actuatormovesbackand
forthnearsetpoint(hunts)
Signalisuctuatingbeyondthe
deadbandsetting
Increasethedeadbandusingthe
Deadbandtrimpot
Signalhasinterference Shieldsignalfrominterference.
Actuator does not travel fully
open or fully closed
Travellimitswitchesarenot
set correctly
Settravellimitswitchesfor90°operation
ServoDIPswitchesarenot
set correctly
SeeQuickSetupInstructionsonpage9.
Mechanicaltravelstopsarenot
set correctly
Setmechanicaltravelstopsjustoutside
theelectricaltravellimitswitchpositions
Actuator motor does not run
ineitherdirectionandthe
greenPowerLEDisoff
PowerdoesnotmatchServoPro
voltageandphase,fuseismissing
orblown,poweristurnedoff
Verifyfuse,verifypowervoltageand
phase,turnpoweron&recalibrate
Actuator motor does not run
ineitherdirectionandthe
greenPowerLEDison
Limitswitchesortorqueswitches
are activated
Verifythatthetravellimitswitchesare
properlyset;verifytorqueswitchesare
presentsorsetcongurationtoTorque
SwitchDisabled
Handwheelisengaged Pushhandwheelin(disengage)
ServoProisnotwiredcorrectly CheckallServoProwiring
Motorhasthermallytripped Allowmotortocooldown
Actuator does not
properly respond to a
commandsignal
Potentiometergearisnotengaged
oradjustedproperly
Engageandadjustpotentiometergear
Commandsignaldoesnotmatch
Congurationswitches
SettheCongurationswitchescorrectly
Commandsignalisfaultyorwired
incorrectly
Verifythevalueofthecommandsignal
withameterandverifythewiringpolarity
is correct.
Actuator runs in one
direction only
Wiringisincorrect CorrectWiring
Potentiometerwiredbackwards
Reversewhiteandgraywires,seewiring
diagraminsidecover
Limitswitchortorqueswitch
is activated
Verifycontinuitybetweenthewirescoming
fromtheswitches.Ifyouractuatorhas
reacheditstravellimit,reversedirection.
Ifoneofyourtorqueswitcheshastripped,
reversetheactuatordirectionandcorrect
theovertorquecondition
Commandsignalisfaultyor
wiredincorrectly
Verifythevalueofthecommandsignal
withameterandverifythewiringpolarity
is correct
6.2 troublesHooting cHart