Servo NXT
Precise modulating control of the valve position.
• Shall accept an analog input command signal
proportional to the desired valve position.
• The analog input signal shall be configurable to either
current or voltage input:
• 4-20mA DC, 0-10V DC, 2-10V DC, 0-5V DC.
• Shall have an analog output retransmission signal
proportional to the actual valve position.
• The analog output signal shall be configurable to either
current or voltage output:
• 4-20mA DC, 0-10V DC, 0-5V DC.
• LED driven menu display shall be provided for simplified
commissioning, monitor and control of actuator.
• Voltage spike and transient protection shall be provided
on all input terminals and output terminals.
• Independent isolation shall be provided between analog
input command signal and output retransmission signal
to eliminate ground loops.
• 120/230VAC units shall have inductive isolation
between line voltage and logic level voltages.
• Control characteristic shall be linear and duty cycle shall
be 100%.
• Calibration shall be accomplished by pressing a single
button to initiate the calibration routine.
• Independent adjustments shall be provided for
deadband and for both open and closed speed control
of the actuator.
• Internal feedback shall be by means of a 10k Ohm
potentiometer.
• Manual mode operation shall be provided to allow
for control of actuator when no command signal is
present.
• On-board fault indications shall be provided.
• Shall be designed to meet UL and CE standards.
Series 70 DeviceNet™
Network control and feedback of valve position.
• Shall be available as an option to provide on/off or
modulating capability.
Actuator Approvals & Certifications
• CE
• Low Voltage Directive: 2014/35/EU
• EMC Directive: 2014/30/EU
• Machinery Directive: 2006/42/EC
• RoHS Directive: 2011/65/EU
• IP65
• ABS
• Bureau Veritas Certification
• CSA Certification
• For select 120VAC units.
• UL Certification (cULus)
• For select 120VAC units.
• NEMA Type 4, 4x.
Hazardous Location
• Certified to UL and CSA standards.
• For select 120VAC units.
• NEMA Type 4x, 7, 9.
• Hazardous location enclosure shall be
UL certified to:
• Class I, DIV 1 & 2, Group C, D
• Class II, DIV 1 & 2, Group E, F, G
• Operating Temperature Code: T3B (165°C)
• All unused conduit entry points to be sealed for ingress
protection.
SERIES 70 ELECTRIC ACTUATORS
Recommended Specifications