Owner's manual

BRAY Series 52 Valve Status Monitor
Operation and Maintenance Manual
14
PROFIBUS DP Version
Specications:
Operating Voltage 24VDC by Probus DP
Target Type Magnetic
Electrical Conguration Probus DP
Maximum Switching
Current 100mA
Consumption Current < 30mA
Output Voltage Drop < 2.5VDC
Addressing 0 to 63 software
congured
Data Bits Input Bit 0: Sensor 1
Input Bit 1: Sensor 2
Output Bit 0: Solenoid
SCHÉMA ÉLECTRIQUE
V -
A
GND
V -
A
GND
B
V +
SOL -
SOL +
NC
RD
YE
B
V +
S1
S2
(WH)
(YE)
(GN)
(BR)
V -
A
GND
B
V +
(WH)
(YE)
(GN)
(BR)
OUT
IN
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
V -
V +
A
B
TERRE
X 10
X 1
SOL -
SOL +
NC
U = 24 V CC - IL = 50 mA
SÉLECTION
D’ADRESSE
RACCORDEMENTS
SUR BORNIER
Step 1: Purchase several
PROFIBUS DP S52s from
your local Bray Distributor
Step 2: Separate the
connection module from the
sensor module by loosening
the two fastening screws.
Step 3: Take an inventory of all com-
ponents of the PROFIBUS DP S52 to
ensure that you have all the necessary
parts of the module. Clockwise from
the top left on the image above, you
should have th following: (a) connec-
tion module, (b) PG connectors, (c)
sensor module, (d) connection plate,
(e) terminal connectors.