Specification Sheet

GAS APPLIANCE CONNECTORS
CONNECTOR MINIMUM FLOW CAPACITY CHARTS
PER ANSI Z21.24 / CSA 6.10 & ANSI Z21.75 / CSA 6.27*
NOTE: Connectors should be sized based upon the appliance gas consumption rate. Select a connector
with a capacity equal to or greater than appliance input rate.
CONNECTOR W/ FITTING OR BALL VALVE
Connector
Series
Nom.
O.D.
Nom.
I.D.
STRAIGHT LENGTH CAPACITY (WATTS PER HOUR) - FOR NATURAL GAS
0.30m (12") 0.46m (18") 0.61m 24" 0.76m (30") 0.91m (36") 1.22m (48") 1.52m (60") 1.83m (72")
CSSL / CSST 3/8" 1/4" 14,067 12,837 11,723 10,668 9,789 8,294 7,297 6,770
CSSD 1/2" 3/8" 29,893 27,285 24,911 22,596 20,837 17,731 15,591 14,390
CSSC 5/8" 1/2" 52,752 48,122 43,961 39,858 36,634 31,066 27,314 25,380
CSSB 7/8" 3/4" 85,254 85,254 85,254 79,276 74,997 63,010 57,852 50,965
0.64 Sp Gr, 1000 BTU per Cu. Ft. (37.2 MJ/m3) gas at 0.5 inch water column (124Pa) pressure drop. Per ANSI Z21.24 / CSA 6.10 and ANSI Z21.75 / CSA 6.27
for use with pressures not to exceed 1/2 PSI.
CONNECTOR W/ APPLIANCE EXCESS FLOW VALVE
Connector
Series
Nom.
O.D.
Nom.
I.D.
STRAIGHT LENGTH CAPACITY
(WATTS PER HOUR) - FOR NATURAL GAS
0.30m (12") 0.46m (18") 0.61m 24" 0.76m (30") 0.91m (36") 1.22m (48") 1.52m (60") 1.83m (72")
CSSL
3/8" 1/4"
14,067
12,837
11,723
10,668
9,789
8,294
7,297
6,770
CSSD 1/2" 3/8"
29,893
27,285
24,911
22,596
20,837
17,731
15,591
14,390
CSSC 5/8" 1/2"
43,921
41,872
40,407
37,479
36,634
31,066
27,314
25,380
CSSB 7/8" 3/4" N/A N/A N/A N/A N/A N/A N/A N/A
0.64 Sp Gr, 1000 BTU per Cu. Ft. (37.2 MJ/m3) gas at 0.5 inch water column (124Pa) pressure drop. Per ANSI Z21.24 / CSA 6.10 and ANSI Z21.75 / CSA 6.27
for use with pressures not to exceed 1/2 PSI.
- Sold with Series 1540 Excess Flow Valve.
- Sold with Series 1550 Excess Flow Valve.
- Sold with Series 1560 Excess Flow Valve.
* The ow capacities in the above charts are the minimum performance criterion established in ANSI Z21.24 • CSA 6.10 and ANSI Z21.75 • CSA 6.27. The ow capacity
of BrassCraft connectors, regardless of end tting or gas ball valve assembly, exceeds these minimum ow requirements.
Manufacturer assumes no responsibility for failure due to improper installation.
©2016 BrassCraft Mfg. Co., Novi, MI 48375-5331 U.S.A. All Rights Reserved. www.brasscraft.com
El fabricante no asume ninguna responsabilidad si la instalación no se hace de acuerdo al instructivo.
©2016 BrassCraft Mfg. Co., Novi, MI 48375-5331 Estados Unidos Todos los derechos reservados. www.brasscraft.com
375.01 REV. 3/16
NATURAL GAS