Specifications

DSE7200 / 7300 Series Operators Manual
34
4.2.3 MAGNETIC PICKUP, CAN AND EXPANSION
PIN
No
DESCRIPTION CABLE
SIZE
NOTES
22 Magnetic pickup Positive
0.5m
AWG 20
Connect to Magnetic Pickup device
23 Magnetic pickup Negative
0.5m
AWG 20
Connect to Magnetic Pickup device
24 Magnetic pickup screen Shield Connect to ground at one end only
25 CAN port H
0.5m
AWG 20
Use only 120 CAN approved cable
26 CAN port L
0.5m
AWG 20
Use only 120 CAN approved cable
27 CAN port Common
0.5m
AWG 20
Use only 120 CAN approved cable
28 +
0.5m
AWG 20
Use only 120 RS485 approved cable
29 -
0.5m
AWG 20
Use only 120 RS485 approved cable
30 SCR
0.5m
AWG 20
Use only 120 RS485 approved cable
NOTE:- Terminals 31 to 38 are not fitted to the 7200 / 7300 controller
NOTE:- Screened cable must be used for connecting the Magnetic Pickup, ensuring that the screen is
earthed at one end ONLY.
NOTE:- Screened 120
impedance cable specified for use with CAN must be used for the CAN link
and the Multiset comms link.
DSE stock and supply Belden cable 9841 which is a high quality 120
impedance cable suitable for CAN
use (DSE part number 016-030)
NOTE:- When the module is configured for CAN operation, terminals 22, 23 & 24 should be left
unconnected. Engine speed is transmitted to the 7000 series controller on the CAN link.
Refer to Electronic Engines and DSE Wiring for further information. Part No. 057-004.