Specifications
DSE7200 / 7300 Series Operators Manual
112
8.14 ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
The ‘running’ editor can be entered while the engine is running. All protections remain active if the engine is
running while the running editor is entered.
Press and hold the button to enter the running editor.
8.14.1 EDITING A PARAMETER
Enter the editor as described above.
Press the
(left) or (right) buttons to cycle to the section you wish to
view/change.
Press the
(up or down) buttons to select the parameter you wish to
view/change within the currently selected section.
To edit the parameter, press to enter edit mode. The parameter begins to flash
to indicate that you are editing the value.
Press the
(up or down) buttons to change the parameter to the required
value.
Press to save the value. The parameter ceases flashing to indicate that it has
been saved.
To exit the editor at any time, press and hold the button.
8.14.2 ADJUSTABLE PARAMETERS (RUNNING EDITOR)
Running Editor (Factory default settings are shown in bold italicised text)
Section
Parameter as shown on display
Factory Setting
DISPLAY
Contrast 50%
Language English
Engine Manual Frequency control (If ‘manual speed control’ is enabled) 0.0Hz
Droop Active / Inactive
Droop 0%
DPTC Auto Regen Inhibit
Active (only available when DPF
Regeneration Control is selected)
DPTC Manual Regen
Inactive (only available when DPF
Regeneration Control is selected)