Reference Guide
The Braeburn Zoning Reference Guide 6 Part No. RG-0508-001
Understanding Bypass System Ductwork
In many zoning installations it is necessary to install a bypass damper. A bypass damper will
help the HVAC equipment maintain rated CFM past the heat exchangers and blower motor. If
a system does not have a bypass, and only a few dampers are open, excess supply plenum
pressure may be created. The result can be system limit trip-outs, excess noise, coil icing, or
other problems. The bypass damper is installed in the bypass system duct.
What is a Bypass System Duct?
It is a connection between the supply side and the return side air plenum. The connection
uses a bypass damper to open when needed. The bypass damper can either be electric, that
opens a damper with an electric motor when needed, or barometric (think barometer) that
opens up a weighted door when the system pressure increases.
Braeburn recommends using one of three methods to control excess supply plenum pressure.
The best method will be determined based on the speci c requirements of the application
such as cost, type of duct system used, actual duct design, and the ability to install a bypass
duct in tight equipment locations.
Three common methods are:
Eliminate the bypass by oversizing each branch of the duct system so that each 1.
branch is capable of owing the system CFM.
return air
ducts
return air
plenum
bypass
duct
coil
supply air
sensor
zone dampers
electric or
barometric
bypass damper
filtration
system
furnace