Reference Guide
Part No. RG-0508-001 15 The Braeburn Zoning Reference Guide
Braeburn 3 Zone Panel Confi guration
Switch
Number
Switch Label Switch Function
1 Non-HP / Heat Pump Conventional or heat pump control of W/Y
2 Normal / Dual Fuel HP 1st stage lockout on 2nd stage call
3 Rev Valve B / O O/B terminal active in heating (B) or cooling (O)
4 Fan Gas / Elec & HP Fan controlled by HVAC system or panel
5 Opp Call 20 / 15 Opposite call answer time in minutes
6 Lockout None / Active 2nd stage lockout without 2 zones calling
7 Priority All / Zone 1 Changeover priority zone 1 or fi rst call
8 G2 W2-Zone / 2 stages High speed fan will come on when 2 zones or
2 stages call
J1 Separate RH RC Remove for dual transformer installation
J2 Short Cycle Protection When on, panel provides compressor short
cycle protection. When off, HVAC equipment
provides short cycle protection
▲
▲
RH
RC
Y1
Y2
G
G2
W1
EH
W2
O/B
C
HI/LOW LIMIT
CUTOUT ADJUST
J2-SHORT CYCLE
PROTECTION
EQUIPMENT
Braeburn
3
-Zon
e
JI REMOVE TO SEPARATE
RH AND RC TERMINAL
SUPPLY TEMP HI TEMP
LO TEMP
PURGE
DELAY
J2 jumper
J1 jumper
HI/LOW
temp cutout
adjustment
HEAT PUMP
DUAL FUEL
O
ELEC/HP
15
ACTIVE
ZONE1
NON HP
NORMAL
REV VALVE B
FAN GAS
OPP CALL 20
LOCKOUT NONE
PRIORITY ALL