Reference Guide

The Braeburn Zoning Reference Guide 14 Part No. RG-0508-001
Confi guring Zone Panels
All Braeburn Zone Panels feature easy to con gure DIP switches that eliminate concerns
about con guration loss after a power failure. The installer can also tell at a glance that the
panel is set up properly prior to leaving the job site. Which is faster for the installer? Go back
through 25 menu steps verses one glance at the DIP switches to insure a panel is set up
properly.
Both the 2-zone and the 3-zone panel use similar DIP switch setup, while the 3-zone has
additional features for temperature control of staging.
Braeburn 2 Zone Panel Confi guration
Switch
Number
Switch Label Switch Function
1 Non-HP / Heat Pump Conventional or heat pump control of W/Y
2 Normal / Dual Fuel HP 1st stage lockout on 2nd stage call
3 Rev Valve B / O O/B terminal active in heating (B) or cooling (O)
4 Fan Gas / Elec & HP Fan controlled by HVAC system or panel
5 Opp Call 20 / 15 Opposite call answer time in minutes
6 Lockout None / Active 2nd stage lockout without 2 zones calling
7 Priority All / Zone 1 Changeover priority zone 1 or fi rst call
J1 Separate RH RC Remove for dual transformer installation
J2 Short Cycle Protection When on, panel provides compressor short cycle
protection. When off, HVAC equipment provides
short cycle protection
FLASHING
WHEN NORMAL
Braeburn
2-Z
o
n
e
JI REMOVE TO SEPARATE
RH AND RC TERMINAL
J2-SHORT CYCLE
PROTECTION
EMERGENCY
HEAT
ON OFF
RH
RC
Y
G
W1
EH
W2
O/B
C
EQUIPMENT
HEAT PUMP
DUAL FUEL
O
ELEC/HP
15
ACTIVE
ZONE1
NON HP
NORMAL
REV VALVE B
FAN GAS
OPP CALL 20
LOCKOUT NONE
PRIORITY ALL
J2 jumper
J1 jumper