Product Overview
©2018 Braeburn Systems LLC • 2215 Cornell Avenue • Montgomery, IL 60538 • All Rights Reserved • 140332-300-02
Zone Panels and Expanders
Description Item No.
2 Zone Economy 2H / 1C 140202
3 Zone Economy 3H / 2C 140303
2 Zone Premier 2H / 1C 140221
3 Zone Premier 3H / 2C 140332
4 Zone Premier 4H / 2C 140404
2 Zone Premier Expander 140424*
* For use with 140404 Zone Panel.
Architectural Specifications
The fully automatic zone panel shall be Braeburn model number 140332, 8.0”W x 10.2”H x 2.1”D, powered from 24 Volts AC. In the event of a power failure, the unit
shall retain all configuration settings. The zone panel shall be compatible with low voltage mechanical or electronic thermostats and be capable of controlling up to
three stages of heating and two stages of cooling. Wiring blocks with terminals R, Y1, Y2, W1/E/AUX, W2/O/B, G, and L shall be included for three thermostats and a
selectable emergency heat position. Equipment terminals Rh, Rc, Y1, Y2, W1/E/AUX, W2/O/B, G, G2, L and C shall be present along with three sets of damper terminals
PO, C, and PC. Configuration options shall be available for System Type-1st Stage/2nd Stage Fan Control for Heating, Reversing Valve, Auxiliary Stage Heat Compres-
sor Lock, Set EM heat Zones, Compressor Balance Point, Auxiliary Balance Point, G2 Staging, Fan Purge Time, Thermostat Type, Equipment Staging Criteria, Staging
Lock, Thermostat
Able to Activate EM Heat, Zone Priority, High Limit Lock, Low Limit Lock, Short Cycle Protection, Temperature Scale, Supply Air Sensor, Opposite
Mode Call Timer, Ad
dress Clear. LED’s (Light Emitting Diodes) shall be present to monitor Panel Power (1), Panel Processor (1), Emergency heat (1), HVAC equipment
terminals (8), three inputs for three thermostats (24), and outputs for three dampers (3). Provisions shall be available to display and adjust high and low temperature
cut out and short cycle protection override. The panel shall have an operating temperature of -22 to 167°F (-30 to 75° C), and a storage temperature of -40 to 167°F
(-40 to 75° C) with an operating humidity range of 5 to 95% RH non-condensing.
Specifications
Power 24 VAC
Outdoor Sensor Optional (Model 5490)
Supply Air Sensor
Optional (Model 149156)
Indicators LED’s for all thermostats, equipment
and dampers, LCD for configuration
Thermostat Conventional or Heat Pump Up to 3H / 2C
Construction PC Board in High Impact Housing
Mounting Wall or Return Air Plenum Mount
Environmental Storage -40˚ F to 167˚ F (-40˚ to 75˚ C)
Operating -22˚ F to 167˚ F (-30˚ to 75˚ C)
The Braeburn Advantage
The Best Value in Zoning Today
®
• Suitable for commercial and residential installation.
• Designed for years of trouble free operation.
• Fully compatible with Braeburn and other zoning
system components.
2.1”
8”
8”
10.2”
Braeburn Thermostats and Accessories
From our Deluxe Series to our economical Builder Series, Braeburn has the products you need to lower energy costs and increase comfort in any home
or business environment. Call Us Toll-Free 866.268.5599 (U.S.) +1.630.844.1968 (Outside the U.S.) www.braeburnonline.com
Dimensions
3 Zone Control Panel 140332