User's Manual

Installer Guide 2
2
Installation and Wireless Setup
Install and Wire the Control Module
1
Wiring Terminations for Control Module
Terminal Conventional Systems Heat Pump Systems
Rh 24VoltACHeatingTransformer 24VoltACTransformer
Rc 24VoltACCoolingTransformer NotUsed
G SystemFanRelay SystemFanRelay
W1/E (W1)1stStageHeatRelay (E)EmergencyHeatRelay
W2/AUX (W2)2ndStageHeatRelay (AUX)AuxiliaryHeatRelay
O/B/V3 (V3)ZoneValvePowerClose (O)CoolActiveReversingValve
(HydronicSystemsOnly) (B)HeatActiveReversingValve
Y1 1stStageCoolingRelay 1stStageCompressorRelay
Y2 2ndStageCoolingRelay 2ndStageCompressorRelay
L NotUsed SystemFaultIndicator
C
24VoltACTransformerCommon
24VoltACTransformerCommon
S1 OptionalWiredRemoteSensor OptionalWiredRemoteSensor
S2 (IndoororOutdoor) (IndoororOutdoor)
P1 RequiredReturnAirPlenum RequiredReturnAirPlenum
P2 Sensor(mustbeinstalled) Sensor(mustbeinstalled)
Warning
Disconnect power before
beginning installation.
Control Module Location
InstallthecontrolmoduleonawallnearHVACequipment
orontheHVACequipment.
•Removethecoverofthecontrolmodule.
•Mountthecontrolmoduleusingthetwomountingholes
andtheappropriatetypeofscrewsfortheapplication.
Install Return Air Sensor (required)
TheReturnAirSensormaintainsdefaulttemperature
controlifwirelesscommunicationislost.
•InstalltheReturnAirSensoratleast12inchesupstream
ofanyhumidicationorventilationequipment.
•ConnecttheReturnAirSensortotheP1andP2
terminals on the control module.
•Forhydronicapplications,mountsensorinanareathat
maintainslivingspacetemperature.Donotmount
onthesupplypipes.
Wiring
Punchout
Mounting
Hole
Mounting
Hole
Wiring
Punchout
Heat Only
Set System Type to 11CONV
Rh
24VoltACPower(heatingtransformer)[note 1]
W1 HeatRelay
G FanRelay[note 3]
C 24VoltACTransformerCommon
1 HEAT / 1 COOL Single or Dual Transformer
Set System Type to 11CONV
Rh
24VoltACPower(heatingtransformer)[note 1]
Rc
24VoltACPower(coolingtransformer)[note 1]
W1 HeatRelay
Y1 CompressorRelay
G FanRelay
C 24VoltACTransformerCommon[note 2]
2 HEAT / 2 COOL Single or Dual transformer
Set System Type to 22CONV
Rh
24VoltACPower(heatingtransformer)[note 1]
Rc
24VoltACPower(coolingtransformer)[note 1]
W1 HeatRelayStage1
W2 HeatRelayStage2
Y1 CompressorRelayStage1
Y2 CompressorRelayStage2 [note 3]
G FanRelay
C 24VoltACTransformerCommon[note 2]
Connect
Button
Rc/RhTerminal
Jumper (J3)