26 Humidification Mode [note 12]–Forusewithanexternalhumidier.Selectsbetweendisabling
humidication(OFF),dependentcontrol(DEP)orindependentcontrol(IND).TheDEPsettingcontrols
humidicationonlyduringacallforheating.TheINDsettingallowshumidicationoutputintheheatmode,
butdoesnotrequireacallforheating.NOTE: It is recommended that the IND setting only be used with
systems designed for low air temperature humidification such as steam humidification. Always ensure the
heat exchanger or other system parts are not exposed to excess water from condensation or other sources.
When there is any doubt, use the OFF or DEP setting.
27 Auto Humidity Set Point Limit [notes 11, 12]–Selectbetweenturningtheautomatic
humiditysetpointlimittoauto(AUTO)ormanual(MAN).WhenAUTOisselected,humiditycontrolisprovided
automaticallybasedontheoutdoortemperature.SelectingMANallowsyoutomanuallycontrolthelevel
ofhumidity.
28 Dehumidification [note 12]–Forusewithanexternaldehumidier.Selectbetweendehumidication
disabled(OFF),anormallyinactive(NI)ornormallyactive(NA)relay,dependingontherequirementsofyour
externaldehumidicationequipment.
29 Installer Clear–Clearssettingsbasedonyourselection.CLROmakesnochanges,CLR1clearsall
wirelessremotesensorconnections,CLR2clearstheconnectiontothecontrolmoduleandCLR3clearsALL
thermostatsettings.
WARNING:IfyoupressNEXT or RETURNafterselectingCLR1,CLR2orCLR3theclearwilltakeplaceand
theappropriatesettingswillbereturnedtofactorydefaults.Ifyoudonotwishtomakeanychanges,usethe
SpeedBar
®
toselectCLRO.