15 AC Power Interrupt Warning [note 6]–Whenenabled,thethermostatwilldisplayanoutagewarning
whenACpowertothethermostatislost.
16 Short Cycle Protection [note 7]–Selectsthenumberofminutesthecoolingcompressorwillbelocked
outafterturningoff.Thisshortcycleprotectionisalsoactiveintheheatmodeifaheatpumpsystemwas
selectedinOption6.
17 Residual Cooling Fan Delay [note 7]–Selectsadelayforthesystemfanafterthecoolingcompressor
hasturnedoff.Thisdelaywillhelpremovetheremainingcoolairoutoftheductworkprovidingadditional
efciency.
18 Adaptive Recovery Mode (early recovery) [note 8]–EnablesordisablestheARM
TM
(adaptiverecovery
mode) feature.DuringARM,roomtemperatureisrecoveredbyturningontheheatingorcoolingbeforethe
endofthesetbackperiod.Thesetpointtemperatureischangedtothatoftheupcomingprogramtemperature.
19 Indoor Remote Sensor Control [note 9]–IfaBraeburn
®
indoorremotesensorisconnected(wired)or
paired(wireless)duringinstallation,thethermostatwillautomaticallydetectthesensor.Whenanindoor
sensorisdetected,youmayselectbetweenthermostatonly(ISENS),remotesensoronly(ESENS)or
combiningthethermostatandtheremotesensor(s)(ASENS).
NOTE: This option does not apply to the Braeburn outdoor sensor. When an outdoor sensor is connected
(wired) or paired (wireless), the thermostat automatically recognizes it and no further configuration
is necessary.
20 Lockout Security Level–Selectsthelevelofkeypadlockoutwhenthethermostatislocked.Level2locks
theentirethermostat(includingthefrontresetbutton).Level1lockseverythingexcepttheSpeedBar
®
allowingforupanddowntemperatureadjustment.NOTE: The lock code is set in the User Settings mode
(see User Manual).
21 Auto Changeover Dead Band [note 10]–Whenautochangeovermodeisenabledinoption5and
selected, the systemautomaticallyswitchesbetweenheatingandcoolingwhentheroomtemperature
meetsthenormalcriteriaforeitheraheatingorcoolingcall.Thereisaforcedseparation(deadband)
betweentheheatingandcoolingsetpointssothatthesystemsdonotworkagainsteachother.This
optionselectstheamountofthisdeadbandindegreeswiththedefaultbeing3°F.
22 Compressor Balance Point [notes 4, 11]–Locksouttheuseofthecompressorheatstagewhenthe
outside air temperatureislessthantheselectedsettingof0°Fto50°F.
23 Auxiliary Heat Balance Point [notes 4, 11]–Locksouttheuseoftheauxiliaryheatstagewhenthe
outside air temperatureexceedstheselectedsettingof70°Fto40°F.NOTE: This balance point over
rides the fossil fuel compressor lockout in option 13. If this option is set to gas and the outdoor
temperature is over the auxiliary balance point, the compressor will remain on during a call for auxiliary heat.
24 Heat Set Point Upper Limit–Selectstheheatingsetpointupperadjustmentlimit.
25 Cool Set Point Lower Limit [note 7]–Selectsthecoolingsetpointloweradjustmentlimit.