Specifications
TDB3108, WF3208 Installation
6 1/23/2013 Bradley • 215-1471 Rev. F; ECN 13-00-001
Type B Drain
Centrally rising vent with
supplies from above
Rough-In Specifications
(mm)
(mm)
Type H Drain
Centrally rising vent with
supplies from below
1" NPT Supplies From Above Must
Reduce to 1/2" Nominal Copper Tube on
These Centers to Pass Thru Washfountain
2" NPT Drain
Through Floor,
Stub Up 3" (76)
Above Floor
1/2" NPT
Vent to
Ceiling
1/2" NPT
Vent to
Ceiling
54" (1372) Bowl
54" (1372) Bowl
1-1/4"
(32)
1-1/4"
(32)
Hot Cold
7/8"
(22)
7/8"
(22)
4"
(102)
Supply lines for one to two
washfountains should be 1"; for three
washfountains 1-1/4". For more than
3 washfountains, pipe sizes should be
increased proportionately.
Supply lines for one to two
washfountains should be 1"; for three
washfountains 1-1/4". For more than
3 washfountains, pipe sizes should be
increased proportionately.
2" NPT Drain:
Stub up 3" (76)
Above Floor
1" NPT Supplies Through Floor,
Stub Up 2-1/2" (64) Above Floor
4"
(102)
7-5/8"
(194)
7-5/8"
(194)
Hot Cold