Installation manual
2
Express® Lavatory System SS-Series
SS-2N/IR/STD, SS-2N/IR/WH Installation Instructions
4/16/04 Bradley Corporation • 215-1497 Rev. B; EN 03-808A
Pre-Installation Information
Barrier-free and ADA compliant - standard height mounting
The SS-2N/IR Express® Lavatory System must have a rim height of 34" above finished floor to be
compliant with Americans with Disabilities Act (ADA). When mounted at 34" rim height, the
Express® meets ADA, ANSI and UFAS requirements for barrier-free clearances, reaches and
controls. Always check local codes and ordinances for compliance.
Barrier-free and ADA compliant - juvenile height mounting
The SS-2N/IR/WH Express® Lavatory System must have a rim height of 31" max. above finished
floor to be compliant with Americans with Disabilities Act (ADA) Accessibility Guidelines for
Buildings and Facilities: Building Elements Designed for Children's Use; Final Rule.
Texas Accessibilities Standards
The SS-2N/IR/WH Express® Lavatory System is designed to comply with Texas Accessibilities
Standards for adults and children. Always check local codes and ordinances for compliance.
Infrared sensor and solenoid
Each sprayhead is controlled by a separate sensor and solenoid valve, enabling each user to activate a
single flow of water. Each valve uses less than half the maximum of hot water allowed by the
ANSI/ASHRAE/IES 90A-1980 Standard.
Supplies required for installation:
• (6) 3/8" wall anchors, bolts and 1" min. O.D. washers to mount main frame and bowl to wall
(minimum pull-out rating of 1,000 lbs.)
• STD. HEIGHT ONLY: (2) 3/8" wall anchors, bolts and 1" min. O.D. washers to mount scuff
base to wall
• 1/2" NPT hot and cold supply piping and 1-1/2" NPT drain piping
• (2) 1/2" NPT street elbows
• 110 volt GFCI protected electrical outlet for 110/24 VAC plug-in transformer (supplied)
• 240/208-volt or 277-volt electrical box for optional electric tankless water heater